5.9 LOGIC CONFIGURATION (PLC EDITOR)
5
After creating the first timer, the second one for output deactivation is made. The set signal will be the virtual output created
as an output of the first timer (VO_100_OUTPUT_ACTIVATION), the reset signal will be the output of the second timer
(VO_100_OUTPUT_DEACTIVATION), the time delay is set as 200 ms.
Once the timing logic (timer 1 + timer 2) has been created, the activation signal (VO_100_OUTPUT_ACTIVATION) is linked
to several virtual outputs. Therefore, virtual outputs (VO_102_OUTPUT_1, VO_103_OUTPUT_2, VO_104_OUTPUT_3,
VO_105_OUTPUT_4) will be activated if the CONT IP_G_CC1(CC1) variable is set to 1. Once the
VO_100_OUTPUT_ACTIVATION is active, it will be deactivated after 200 ms, and will remain deactivated for 5 seconds.
This process will be repeated while the digital input is active.
To finish the process the logic must be compiled (
Run >Compile
) and the equations sent to the relay (
Run >Send
Equations to relay
) to start working with the new logic.