GEK-113285A
G650 Generator Protection & Control System
2-19
2 PRODUCT DESCRIPTION
2.4 TECHNICAL SPECIFICATIONS
2
2.4.2.6 FREQUENCY RATE OF CHANGE
df/dt trend
increasing, decreasing, bi-directional
df/dt pickup level
0.10 to 10.00 Hz/s in steps of 0.01
df/dt level accuracy
80 mHz/s or 3.5%, whichever is greater
Overvoltage supv.
0.00 to 110.00 % in steps of 0.01
95% settling time for df/dt
< 24 cycles
Operate time:
at 2 x pickup
12 cycles
at 3 x pickup
8 cycles
at 5 x pickup
6 cycles
Frequency Rate min.
20.00 to 80.00 Hz in steps of 0.01
Frequency Rate max.
20.00 to 80.00 Hz in steps of 0.01
Frequency Rate delay
0.00 to 60.00 s in steps of 0.01
Snapshot Events
Selectable by setting