GEK-113285A
G650 Generator Protection & Control System
5-85
5 SETTINGS
5.5 CONTROL ELEMENTS
5
Table 5–83: SYNCHRONISM CONDITIONS
Table 5–83: shows the different synchrocheck and closing logic situations, that can be produced depending on the line and
busbar voltage levels.
Live Line – Live Bus (Synchronism check):
Only in case number (2), with live line and live bus, the element will start
evaluating the line and busbar voltage comparison with respect to the setting
Δ
V
set
established by setting (Max Volt Difference). In this case, if the voltage difference is
lower than
Δ
V
set
, the synchronism check element (25) will verify the angle difference
Δϕ
adjusted by setting (Max Angle Difference).
Dead Line – Dead Bus (DL - DB):
Case number (3) will not allow the synchronism function, but it will allow DL-DB
operation logic, if this logic is enabled by setting (DL-DB Function).
Dead Line – Live Bus (DL - LB):
Case number (6) will not allow the synchronism function, but it will allow DL-LB
Operation logic, if this logic is enabled by setting (DL-LB Function)
Live Line – Dead Bus (LL - DB):
Case number (7) will not allow the synchronism function, but it will allow LL-DB
operation logic, if this logic is enabled by setting (LL-DB Function)
Case numbers (1), (4) and (5) are not considered neither for synchronism check purposes, nor for closing logic.
SYNCHRONISM SITUATION SYNCHRONISM
CHECK
CLOSING LOGIC
LINE VOLTAGE
LEVELS
BUSBAR VOLTAGE
LEVELS
(1) V
L
< (V
1
& V
2
)< V
H
Not permitted
Not permitted
V1 > dead line level
V1 < live line level
V2 > dead bus level
V2 < live bus level
(2) (V
1
& V
2
) > V
H
Permitted
Live Line – Live Bus
V1 > live line level
V2 > live bus level
(3) (V
1
& V
2
) <
V
L
Not permitted
Dead Line – Dead Bus
V1 < dead line level
V2 < dead bus level
(4) (V
1
< V
L
) & (V
L
< V
2
< V
H
) Not permitted
Not permitted
V1 < dead line level
V2 > dead bus level
V2 < live bus level
(5) (V
2
<
V
L
) & (V
L
< V
1
< V
H
) Not permitted
Not permitted
V1 > dead line level
V1 < live line level
V2 < dead bus level
(6) (V
1
<
V
L
) & (V
2
> V
H
)
Not permitted
Dead Line – Live Bus
V1 < dead line level
V2 > live bus level
(7) (V
2
<
V
L
) & (V
1
> V
H
)
Not permitted
Live Line – Dead Bus
V1 > live line level
V2 < dead bus level
Summary of Contents for Multilin G650
Page 9: ...8 G650 Generator Protection Control System GEK 113285A TABLE OF CONTENTS ...
Page 426: ...GEK 113285A G650 Generator Protection Control System A 31 APPENDIX A A 1 LOGIC OPERANDS A ...
Page 427: ...A 32 G650 Generator Protection Control System GEK 113285A A 1 LOGIC OPERANDS APPENDIXA A ...
Page 587: ...C 22 G650 Generator Protection Control System GEK 113285A C 8 ANALOG INPUTS APPENDIXC C ...
Page 639: ...G 2 G650 Generator Protection Control System GEK 113285A G 1 GE MULTILIN WARRANTY APPENDIXG G ...