B-132
G650 Generator Protection & Control System
GEK-113285A
B.7 MEMORY MAP
APPENDIX B
B
Ajustes Imagen Térmica Generador Grupo 1 - Generator Thermal Model 1 Settings
0x43AD
Function
F012
1
R/W
1
0=DISABLED
1=ENABLED
0x43AE
Heat Time Constant
F003
1
R/W
2
[3.0 , 600.0] min
0x43B0
Cool Time Constant
F003
1
R/W
2
[1.00 , 6.00]
0x43B2
Pickup Level
F003
1
R/W
2
[0.05 , 160.00] A
0x43B4
Alarm Level
F003
1
R/W
2
[1.0 , 110.0] %
0x43B6
Constant K1
F003
1
R/W
2
[1.0 , 8.0]
0x43B8
Snapshot Events
F012
1
R/W
1
0=DISABLED
1=ENABLED
0x43C2
Confirmation address
W
1
Ajustes Imagen Térmica Generador Grupo 2 - Generator Thermal Model 2 Settings
0x43C3
Function
F012
1
R/W
1
0=DISABLED
1=ENABLED
0x43C4
Heat Time Constant
F003
1
R/W
2
[3.0 , 600.0] min
0x43C6
Cool Time Constant
F003
1
R/W
2
[1.00 , 6.00]
0x43C8
Pickup Level
F003
1
R/W
2
[0.05 , 160.00] A
0x43CA
Alarm Level
F003
1
R/W
2
[1.0 , 110.0] %
0x43CC
Constant K1
F003
1
R/W
2
[1.0 , 8.0]
0x43CE
Snapshot Events
F012
1
R/W
1
0=DISABLED
1=ENABLED
0x43D8
Confirmation address
W
1
Ajustes Imagen Térmica Generador Grupo 3 - Generator Thermal Model 3 Settings
0x43D9
Function
F012
1
R/W
1
0=DISABLED
1=ENABLED
0x43DA
Heat Time Constant
F003
1
R/W
2
[3.0 , 600.0] min
0x43DC
Cool Time Constant
F003
1
R/W
2
[1.00 , 6.00]
0x43DE
Pickup Level
F003
1
R/W
2
[0.05 , 160.00] A
0x43E0
Alarm Level
F003
1
R/W
2
[1.0 , 110.0] %
0x43E2
Constant K1
F003
1
R/W
2
[1.0 , 8.0]
0x43E4
Snapshot Events
F012
1
R/W
1
0=DISABLED
1=ENABLED
0x43EE
Confirmation address
W
1
Ajustes Limitador Factor de Potencia Grupo 1 - Pwr Factor Limiting 1 Settings(Enhanced models only)
0x43EF
Function
F012
1
R/W
1
0=DISABLED
1=ENABLED
0x43F0
PF Lead Stg1 Level
F003
1
R/W
2
[0.05 , 0.99]
0x43F2
PF Lag Stg1 Level
F003
1
R/W
2
[0.05 , 0.99]
0x43F4
PF Stg1 Trip Delay
F003
1
R/W
2
[0.2 , 300.0] s
0x43F6
PF Lead Stg2 Level
F003
1
R/W
2
[0.05 , 0.99]
0x43F8
PF Lag Stg2 Level
F003
1
R/W
2
[0.05 , 0.99]
0x43FA
PF Stg2 Trip Delay
F003
1
R/W
2
[0.2 , 300.0] s
0x43FC
Snapshot Events
F012
1
R/W
1
0=DISABLED
1=ENABLED
0x4406
Confirmation address
W
1
Ajustes Limitador Factor de Potencia Grupo 2 - Pwr Factor Limiting 2 Settings(Enhanced models only)
0x4407
Function
F012
1
R/W
1
0=DISABLED
1=ENABLED
0x4408
PF Lead Stg1 Level
F003
1
R/W
2
[0.05 , 0.99]
0x440A
PF Lag Stg1 Level
F003
1
R/W
2
[0.05 , 0.99]
0x440C
PF Stg1 Trip Delay
F003
1
R/W
2
[0.2 , 300.0] s
0x440E
PF Lead Stg2 Level
F003
1
R/W
2
[0.05 , 0.99]
0x4410
PF Lag Stg2 Level
F003
1
R/W
2
[0.05 , 0.99]
ADDRESS BIT
NAME
FORMAT
STEP MODE LENGTH
MISCELLANEOUS
Summary of Contents for Multilin G650
Page 9: ...8 G650 Generator Protection Control System GEK 113285A TABLE OF CONTENTS ...
Page 426: ...GEK 113285A G650 Generator Protection Control System A 31 APPENDIX A A 1 LOGIC OPERANDS A ...
Page 427: ...A 32 G650 Generator Protection Control System GEK 113285A A 1 LOGIC OPERANDS APPENDIXA A ...
Page 587: ...C 22 G650 Generator Protection Control System GEK 113285A C 8 ANALOG INPUTS APPENDIXC C ...
Page 639: ...G 2 G650 Generator Protection Control System GEK 113285A G 1 GE MULTILIN WARRANTY APPENDIXG G ...