C-8
G650 Generator Protection & Control System
GEK-113285A
C.3 IMPLEMENTATION TABLE
APPENDIX C
C
b) IMPLEMENTATION TABLE (SHEET 2 OUT OF 3)
Note 1: A default variation refers to the variation responded when variation 0 is requested and/or in class 0, 1, 2, or 3 scans.
Note 2: For static (non-change-event) objects, qualifiers 17 or 28 are only responded when a request is sent with qualifiers 17 or 28,
respectively. Otherwise, static object requests sent with qualifiers 00, 01, 06, 07, or 08, will be responded with qualifiers 00 or 01
(for change-event objects, qualifiers 17 or 28 are always responded).
Note 3: Cold restarts are implemented the same as warm restarts – The G650 is not restarted, but the DNP process is restarted.
OBJECT
REQUEST
RESPONSE
Object
No.
Variation
No.
Description
Function Codes
(dec)
Qualifier Codes (hex) Function Codes Qualifier Codes
(hex)
21
0
Frozen Counter - All Variations
1
(read)
06
(no range, or all)
22
0
Counter Change Event - All
Variations
1
(read)
06
(no range, or all)
07,08
(limited qty)
30
0
Analog Input - All Variations
1
(read)
22
(assign class)
06
(no range, or all)
00,01
(start-stop)
07,08
(limited qty)
17,28
(index)
30
1
32-Bit Analog Input
See Note 1
1
(read)
22
(assign class)
000,01
(start-stop)
06
(no range, or all)
07,08
(limited qty)
17,28
(index)
129
(response)
00, 01
(start-
stop)
17,28
(index)
See Note 2
30
2
16-Bit Analog Input
1
(read)
22
(assign class)
00,01
(start-stop)
06
(no range, or all)
07,08
(limited qty)
17,28
(index)
129
(response)
00, 01
(start-
stop)
17,28
(index)
See Note 2
30
3
32-Bit Analog Input without Flag
1
(read)
22
(assign class)
00,01
(start-stop)
06
(no range, or all)
07,08
(limited qty)
17,28
(index)
129
(response)
00, 01
(start-
stop)
17,28
(index)
See Note 2
30
4
16-Bit Analog Input without Flag
1
(read)
22
(assign class)
00,01
(start-stop)
06
(no range, or all)
07,08
(limited qty)
17,28
(index)
129
(response)
00, 01
(start-
stop)
17,28
(index)
See Note 2
32
0
Analog Change Event - All Variations 1
(read)
06
(no range, or all)
07,08
(limited qty)
32
1
32-Bit Analog Change Event without
Time
See Note 1
1
(read)
06
(no range, or all)
07,08
(limited qty)
129
(response)
130
(unsol.resp)
17, 28
(index)
32
2
16-Bit Analog Change Event without
Time
1
(read)
06
(no range, or all)
07,08
(limited qty)
129
(response)
130
(unsol.resp)
17, 28
(index)
32
3
32-Bit Analog Change Event with
Time
1
(read)
06
(no range, or all)
07,08
(limited qty)
129
(response)
130
(unsol.resp)
17,28
(index)
32
4
16-Bit Analog Change Event with
Time
1
(read)
06
(no range, or all)
07,08
(limited qty)
129
(response)
130
(unsol.resp)
17,28
(index)
34
0
Analog Input Reporting Deadband
1
(read)
00,01
(start-stop)
06
(no range, or all)
07,08
(limited qty)
17,28
(index)
34
1
16-Bit Analog Input Reporting
Deadband
See Note 1
1
(read)
00,01
(start-stop)
06
(no range, or all)
07,08
(limited qty)
17,28
(index)
129
(response)
00,01
(start-
stop)
17,28
(index)
See Note 2
Summary of Contents for Multilin G650
Page 9: ...8 G650 Generator Protection Control System GEK 113285A TABLE OF CONTENTS ...
Page 426: ...GEK 113285A G650 Generator Protection Control System A 31 APPENDIX A A 1 LOGIC OPERANDS A ...
Page 427: ...A 32 G650 Generator Protection Control System GEK 113285A A 1 LOGIC OPERANDS APPENDIXA A ...
Page 587: ...C 22 G650 Generator Protection Control System GEK 113285A C 8 ANALOG INPUTS APPENDIXC C ...
Page 639: ...G 2 G650 Generator Protection Control System GEK 113285A G 1 GE MULTILIN WARRANTY APPENDIXG G ...