2-30
G650 Generator Protection & Control System
GEK-113285A
2.4 TECHNICAL SPECIFICATIONS
2 PRODUCT DESCRIPTION
2
Protocols available:
ModBus
®
RTU / DNP 3.0
Typical distance:
1200 m
Isolation:
2 kV
CAN PORT:
Rear port:
CAN port in models X, Y, Z for asynchronous rear ports
Type:
Multimode glass F.O. port with ST connectors
Fiber Wave length:
1300 nm
Fiber type:
multimode 62.5/125
μ
m or 50/125
μ
m
Maximum recommended length
500m
Isolation:
2 kV
ETHERNET PORT:
Rear port:
COM3
Type (depending on model):
Model B:
10/100BaseTX self-negotiable
Model C:
10/100 100Base FX
Model D:
10/100 redundant 100BaseFX (Physical media redundancy)
Model E:
Redundant 10/100BaseTX self-negotiable ports
10/100BaseTX
RJ45 connector
100BaseFX
ST connectors
Wave length:
1300 nm
Fiber type:
multimode 62.5/125
μ
m or 50/125
μ
m
Protocols available:
ModBus® TCP/IP
DNP over TCP/IP and UDP/IP
Http, ftp, tftp (allow the use of a standard Internet browser)
Typical distance:
1.65 km
Response time to ModBus commands: 10 ms Typical
Isolation:
2 kV
In Models C and D, the 10/100BaseTX port is selected by an internal switch (see 3.3.3)
Two witness LED’s for transmission and reception are included
Summary of Contents for Multilin G650
Page 9: ...8 G650 Generator Protection Control System GEK 113285A TABLE OF CONTENTS ...
Page 426: ...GEK 113285A G650 Generator Protection Control System A 31 APPENDIX A A 1 LOGIC OPERANDS A ...
Page 427: ...A 32 G650 Generator Protection Control System GEK 113285A A 1 LOGIC OPERANDS APPENDIXA A ...
Page 587: ...C 22 G650 Generator Protection Control System GEK 113285A C 8 ANALOG INPUTS APPENDIXC C ...
Page 639: ...G 2 G650 Generator Protection Control System GEK 113285A G 1 GE MULTILIN WARRANTY APPENDIXG G ...