2-14
G650 Generator Protection & Control System
GEK-113285A
2.4 TECHNICAL SPECIFICATIONS
2 PRODUCT DESCRIPTION
2
2.4.1.16 PHASE UNDERVOLTAGE (27P)
2.4.1.17 NEUTRAL OVERVOLTAGE (59NH)
2.4.1.18 GROUND OVERVOLTAGE (59G)
Voltage Input
Fundamental Phasor of phase-to-ground or phase-to-
phase voltages (selectable by setting)
Pickup level
3 to 500 in steps of 1 V
Dropout level
102% to 103% of the pickup level
Level accuracy
±
1% reading
±
0.1% Full Scale from 10 to 500 V at
nominal frequency
Curve Shapes
Fixed time or inverse curve
Reset type
Instantaneous
Curve Multiplier (Time Dial)
0.00 to 900.00 s. in steps of 0.01 s.
Timing accuracy
±3.5% of operate time or 50 ms. (whichever is greater)
Minimum Voltage Threshold
0 to 500 in steps of 1 V
Logic
Any/Two/All phases logic selectable by setting
Supervised by Breaker
Selectable by setting
Snapshot Events
Selectable by setting
Voltage Input
Fundamental Phasor of the neutral voltage (calculated
from phases)
Pickup level
3 to 500 in steps of 1 V
Dropout level
97% to 98% of the pickup level
Level accuracy
±
1% reading
±
0.1% Full Scale from 10 to 500 V at
nominal frequency
Trip delay
0.00 to 900.00 s. in steps of 0.01 s
Reset delay
0.00 to 900.00 s. in steps of 0.01 s
Timing accuracy
±3.5% of operate time or 50 ms. (whichever is greater)
Snapshot Events
Selectable by setting
Voltage Input
Fundamental Phasor of the ground voltage (measured
from 4th voltage transformer)
Pickup level
3 to 500 in steps of 1 V
Dropout level
97% to 98% of the pickup level
Level accuracy
±
1% reading
±
0.1% Full Scale from 10 to 500 V at
nominal frequency
Trip delay
0.00 to 900.00 s. in steps of 0.01 s
Reset delay
0.00 to 900.00 s. in steps of 0.01 s
Timing accuracy
±3.5% of operate time or 50 ms. (whichever is greater)
Snapshot Events
Selectable by setting
Summary of Contents for Multilin G650
Page 9: ...8 G650 Generator Protection Control System GEK 113285A TABLE OF CONTENTS ...
Page 426: ...GEK 113285A G650 Generator Protection Control System A 31 APPENDIX A A 1 LOGIC OPERANDS A ...
Page 427: ...A 32 G650 Generator Protection Control System GEK 113285A A 1 LOGIC OPERANDS APPENDIXA A ...
Page 587: ...C 22 G650 Generator Protection Control System GEK 113285A C 8 ANALOG INPUTS APPENDIXC C ...
Page 639: ...G 2 G650 Generator Protection Control System GEK 113285A G 1 GE MULTILIN WARRANTY APPENDIXG G ...