GEK-113285A
G650 Generator Protection & Control System
10-3
10 APPLICATION EXAMPLES
10.1 EXAMPLE 1: COMMUNICATION & PROTECTION SETTINGS PROCEDURE
10
10.1.3 PROCEDURE TO SET THE PROTECTION FUNCTION
Once the relay has been connected set protection functions and outputs according to the following steps:
Open EnerVista 650 SETUP program and under:
SETPOINT
⇓
SYSTEM SETUP
⇒
⇓
GENERAL SETTINGS
Under
SETPOINT
⇓
PROTECTION ELEMENTS
⇒
⇓
PHASE CURRENT
⇒
⇓
PHASE TOC HIGH
⇒
PHASE TOC HIGH
1
Under
SETPOINT
⇓
CONTROL ELEMENTS
⇒
INPUTS/OUTPUTS
⇒
BOARD F
Under
SETPOINT
⇓
RELAY CONFIGURATION
⇒
OUTPUTS
NAME
VALUE
Phase CT Ratio
1.0 (default)
Ground CT Ratio
1.0 (default)
Stv Ground CT Ratio
1.0 (default)
Phase VT Ratio
1.0 (default)
Phase VT Connection
Wye
Nominal Voltage
100.0 (default)
Nominal Frequency
50
Phase Rotation
ABC
Frequency Reference
VI (default)
Auxiliary Voltage
VX (default)
Snapshot Events
Disabled (default)
Freq. Tracking
Disabled (default)
NAME
VALUE
Function
Enabled
Input
Phasor DFT
Pickup Level
5.0 A
Curve
IEC Curve A
TD Multiplier
0.1
Reset
Instantaneous
Voltage Restraint
Disabled
NAME
VALUE
Output Logic_00_00
Positive
Output Type_00_00
Latch
SELECT
NAME
SOURCE
OR
Contact Output Operate 00 (Board F)
C Output Oper_00_00
PRESS FOR LOGIC
Phase TOC A Op
Phase TOC B Op
Phase TOC C Op
Contact Output Reset 00 (Board F)
C Output Reset_00_00
Operation bit 000
Summary of Contents for Multilin G650
Page 9: ...8 G650 Generator Protection Control System GEK 113285A TABLE OF CONTENTS ...
Page 426: ...GEK 113285A G650 Generator Protection Control System A 31 APPENDIX A A 1 LOGIC OPERANDS A ...
Page 427: ...A 32 G650 Generator Protection Control System GEK 113285A A 1 LOGIC OPERANDS APPENDIXA A ...
Page 587: ...C 22 G650 Generator Protection Control System GEK 113285A C 8 ANALOG INPUTS APPENDIXC C ...
Page 639: ...G 2 G650 Generator Protection Control System GEK 113285A G 1 GE MULTILIN WARRANTY APPENDIXG G ...