10-6
G650 Generator Protection & Control System
GEK-113285A
10.2 EXAMPLE 2: PROCEDURE TO SET AN OPERATION
10 APPLICATION EXAMPLES
10
Under
SETPOINT
⇓
RELAY CONFIGURATION
⇒
OPERATIONS
Select
Operation 0
Command Text
Close C_Output_00_00
Interlock Type
None
Interlocks
---
Final State Type
None
Final States
---
Frontal Key
F2
Contact Input
None
Virtual Output
None
Time Out
500 (default)
MMI
---
Com1
---
Com 2
---
ETH-Master 1
---
ETH Master 2
---
ETH Master 3
---
ETH Mastef 4
---
In the same window (next rows)
Select
Operation 1
Command Text
Reset C_Output_00_00
Interlock Type
None
Interlocks
---
Final State Type
None
Final States
---
Frontal Key
F1
Contact Input
None
Virtual Output
None
Time Out
500 (default)
MMI
---
Com1
---
Com 2
---
ETH-Master 1
---
ETH Master 2
---
ETH Master 3
---
ETH Mastef 4
---