G650 Generator Protection & Control System
GEK-113285A
B.7 MEMORY MAP
APPENDIX B
B
0x38E3
Data Logger Chnl 14
F004
1
R/W
1
[0 , 32767]
0x38E4
Data Logger Chnl 15
F004
1
R/W
1
[0 , 32767]
0x38E5
Data Logger Chnl 16
F004
1
R/W
1
[0 , 32767]
0x38F9
Confirmation
address
W
1
Ajustes unidad direccional de potencia Grupo 1 - Directional Power 1 Settings
0x38FA
Function
F012
1
R/W
1
0=DISABLED
1=ENABLED
0x38FB
Blk Time After Close
F003
1
R/W
2
[0,00 , 900,00] s
0x38FD
Dir Power Angle 1
F003
1
R/W
2
[0,00 , 359,99] Deg
0x38FF
Stage 1 Tap
F003
1
R/W
2
[-10000,00 , 10000,00] MW
0x3901
Stage 1 Time
F003
1
R/W
2
[0,00 , 900,00] s
0x3903
Dir Power Angle 2
F003
1
R/W
2
[0,00 , 359,99] Deg
0x3905
Stage 2 Tap
F003
1
R/W
2
[-10000,00 , 10000,00] MW
0x3907
Stage 2 Time
F003
1
R/W
2
[0,00 , 900,00] s
0x3909
Snapshot
Events
F012
1
R/W
1
0=DISABLED
1=ENABLED
0x391C
Confirmation
address
W
1
Ajustes unidad direccional de potencia Grupo 2 - Directional Power 2 Settings
0x391D
Function
F012
1
R/W
1
0=DISABLED
1=ENABLED
0x391E
Blk Time After Close
F003
1
R/W
2
[0,00 , 900,00] s
0x3920
Dir Power Angle 1
F003
1
R/W
2
[0,00 , 359,99] Deg
0x3922
Stage 1 Tap
F003
1
R/W
2
[-10000,00 , 10000,00] MW
0x3924
Stage 1 Time
F003
1
R/W
2
[0,00 , 900,00] s
0x3926
Dir Power Angle 2
F003
1
R/W
2
[0,00 , 359,99] Deg
0x3928
Stage 2 Tap
F003
1
R/W
2
[-10000,00 , 10000,00] MW
0x392A
Stage 2 Time
F003
1
R/W
2
[0,00 , 900,00] s
0x392C
Snapshot
Events
F012
1
R/W
1
0=DISABLED
1=ENABLED
0x393F
Confirmation
address
W
1
Ajustes unidad direccional de potencia Grupo 3 - Directional Power 3 Settings
0x3940
Function
F012
1
R/W
1
0=DISABLED
1=ENABLED
0x3941
Blk Time After Close
F003
1
R/W
2
[0,00 , 900,00] s
0x3943
Dir Power Angle 1
F003
1
R/W
2
[0,00 , 359,99] Deg
0x3945
Stage 1 Tap
F003
1
R/W
2
[-10000,00 , 10000,00] MW
0x3947
Stage 1 Time
F003
1
R/W
2
[0,00 , 900,00] s
0x3949
Dir Power Angle 2
F003
1
R/W
2
[0,00 , 359,99] Deg
0x394B
Stage 2 Tap
F003
1
R/W
2
[-10000,00 , 10000,00] MW
0x394D
Stage 2 Time
F003
1
R/W
2
[0,00 , 900,00] s
0x394F
Snapshot
Events
F012
1
R/W
1
0=DISABLED
1=ENABLED
0x3962
Confirmation
address
W
1
Ajustes Sincronizacion SNTP - SNTP synchronization Settings (Do not apply to C650 models)
SNTP
0x3F5C
Function
F012
1
R/W
1
0=DISABLED
1=UNICAST
2=BROADCAST
3=ANYCAST
0x3F5D
UDP Port
F005
1
R/W
2
[1 , 65535]
0x3F5F
Server IP Oct 1
F004
1
R/W
1
[0 , 255]
0x3F60
Server IP Oct 2
F004
1
R/W
1
[0 , 255]
ADDRESS BIT
NAME
FORMAT
STEP MODE LENGTH
MISCELLANEOUS
Summary of Contents for Multilin G650
Page 9: ...8 G650 Generator Protection Control System GEK 113285A TABLE OF CONTENTS ...
Page 426: ...GEK 113285A G650 Generator Protection Control System A 31 APPENDIX A A 1 LOGIC OPERANDS A ...
Page 427: ...A 32 G650 Generator Protection Control System GEK 113285A A 1 LOGIC OPERANDS APPENDIXA A ...
Page 587: ...C 22 G650 Generator Protection Control System GEK 113285A C 8 ANALOG INPUTS APPENDIXC C ...
Page 639: ...G 2 G650 Generator Protection Control System GEK 113285A G 1 GE MULTILIN WARRANTY APPENDIXG G ...