GEK-113285A
G650 Generator Protection & Control System
B-75
APPENDIX B
B.7 MEMORY MAP
B
Ajustes Sobreintensidad Temporizada de Tierra Sensible Grupo 1 - Sensitive Ground TOC 1 Settings (Enhanced models only)(cont.)
12=ANSI Very Inv
13=ANSI Norm Inv
14=ANSI Mod Inv
15=I2t
16=Definite
Time
17=Rectifier
Curve
18=User Curve A
19=User Curve B
20=User Curve C
21=User Curve D
0x24A6
TD Multiplier
F003
1
R/W
2
[0.00 , 900.00] s
0x24A8
Reset
F012
1
R/W
1
0=INSTANTANEOUS
1=LINEAR
0x24A9
Snapshot
Events
F012
1
R/W
1
0=DISABLED
1=ENABLED
0x24BC
Confirmation
address
W
1
Ajustes Sobreintensidad Temporizada de Tierra Sensible Grupo 2 - Sensitive Ground TOC 2 Settings (Enhanced models only)
0x24BD
Function
F012
1
R/W
1
0=DISABLED
1=ENABLED
0x24BE
Input
F012
1
R/W
1
0=PHASOR(DFT)
1=RMS
0x24BF
Pickup Level
F003
1
R/W
2
[0.005 , 16.000] A
0x24C1
Curve
F012
1
R/W
1
0=IEEE Ext Inv
1=IEEE Very Inv
2=IEEE Mod Inv
3=IEC Curve A
4=IEC Curve B
5=IEC Curve C
6=IEC Long-Time Inv
7=IEC Short-Time Inv
8=IAC Ext Inv
9=IAC Very Inv
10=IAC Mod Inv
11=ANSI Ext Inv
12=ANSI Very Inv
13=ANSI Norm Inv
14=ANSI Mod Inv
15=I2t
16=Definite
Time
17=Rectifier
Curve
18=User Curve A
19=User Curve B
20=User Curve C
21=User Curve D
0x24C2
TD Multiplier
F003
1
R/W
2
[0.00 , 900.00] s
0x24C4
Reset
F012
1
R/W
1
0=INSTANTANEOUS
1=LINEAR
0x24C5
Snapshot
Events
F012
1
R/W
1
0=DISABLED
1=ENABLED
0x24D8
Confirmation
address
W
1
ADDRESS BIT
NAME
FORMAT
STEP MODE LENGTH
MISCELLANEOUS
Summary of Contents for Multilin G650
Page 9: ...8 G650 Generator Protection Control System GEK 113285A TABLE OF CONTENTS ...
Page 426: ...GEK 113285A G650 Generator Protection Control System A 31 APPENDIX A A 1 LOGIC OPERANDS A ...
Page 427: ...A 32 G650 Generator Protection Control System GEK 113285A A 1 LOGIC OPERANDS APPENDIXA A ...
Page 587: ...C 22 G650 Generator Protection Control System GEK 113285A C 8 ANALOG INPUTS APPENDIXC C ...
Page 639: ...G 2 G650 Generator Protection Control System GEK 113285A G 1 GE MULTILIN WARRANTY APPENDIXG G ...