5-70
G650 Generator Protection & Control System
GEK-113285A
5.4 PROTECTION ELEMENTS
5 SETTINGS
5
Table 5–71: VOLTS PER HERTZ ELEMENT SETTINGS
•
Function
: This setting allows enabling or disabling the Volts per Hertz element.
•
V/Hz Source
: This setting allows the user to select the voltage used to calculate the Volt/Hz ratio. If V/Hz source is
configured as “PHASE”, the maximum phase among the three voltage channels at any given point in time is the input
voltage signal for element operation (Va, Vb, Vc for WYE conection or Vab, Vbc, Vca for DELTA conection). If V/Hz
source is configured as “AUX VOLTAGE”, the element will use the voltage measured through the fourth voltage
transformer (A11-A12).
•
V/Hz Minimum Voltage:
Minimum operating voltage for this unit, if the voltage in any of the phases or in the auxiliary
voltage input (depending on the V/Hz source setting) is below this value the function will be inhibited.
•
V/Hz Pickup Level
: This setting defines the Volts/Hz level to operate. The unit used for this setting is pu value defined
as 1 pu = Nominal Voltage Setting/ System frequency Setting.
•
V/Hz Curve
: This setting allows the user to select between "Definite Time" or "Inverse Curve" types A, B or C.
•
V/Hz TD Multiplier
: In case of having selected "Definite Time", this setting defines the time in seconds. Instantaneous
trips are obtained settings a zero value. Otherwise is the TD multiplier for the inverse curve selected in V/Hz curve
setting.
•
V/Hz T-Reset Delay
: The element has a linear reset characteristic. The reset delay can be programmed to match the
cooling characteristics of the protected equipment. The element will fully reset from the trip threshold in Volts/Hz T-
Reset seconds.
•
Snapshot events
:The snapshot event setting enables or disables the snapshot event generation for this element.
Table 5–72: VOLTS PER HERTZ INTERNAL SIGNALS
5.4.9.8 GROUND OVERVOLTAGE ELEMENT (59G)
G650 provides one ground overvoltage element. This function takes the measurement from the auxiliary voltage VTwhen
VG is selected as Auxiliary Voltage in General Settings. The time delay for the 59G element can be set from 0 to 900
seconds, the element has a reset time setting that can be programmed from 0 to 900 seconds.
SETPOINT > PROTECTION ELEMENTS > VOLTAGE ELEMENTS > VOLTS PER HERTZ >
VOLTS PER HERTZ 1> VOLTS PER HERTZ 2 > VOLTS PER HERTZ 3
SETTING DESCRIPTION
NAME
DEFAULT VALUE
STEP
RANGE
Function permission
Function
DISABLED
N/A
[DISABLED – ENABLED]
V/Hz Source for element calculations
V/Hz Source
PHASES
N/A
[PHASES – AUX VOLTAGE]
V/Hz Minimum operating Voltage
V/Hz Minimum Voltage 40.00
0.01 V
[30.00 : 500.00]
V/Hz Pickup Level
V/Hz Pickup Level
1.00
0.01 pu
[0.80 : 4.00]
V/Hz Curve
V/Hz Curve
DEFINITE TIME
[DEFINITE TIME-CURVE A-
CURVE B – CURVE C]
V/Hz TD Multiplier
V/Hz TD Multiplier
1.00
0.01
[0.05 : 600.00]
V/Hz Reset Delay
V/Hz Reset Delay
1.0
0.1 s
[0.0 : 900.0]
Snapshot Event generation
Snapshot Events
ENABLED
N/A
[DISABLED – ENABLED]
Signal
Comment
Volts/Hz (1, 2,3) BLOCK
Input used to block the (1, 2, 3) element externally
(configurable in Setpoint>Relay
Configuration>Protection Elements)
Volts/Hz (1, 2,3) PKP
Output used to indicate a pickup of the (1, 2, 3)
element
Volts/Hz (1, 2,3) OP
Output used to indicate an operation of the (1, 2, 3)
element.
Summary of Contents for Multilin G650
Page 9: ...8 G650 Generator Protection Control System GEK 113285A TABLE OF CONTENTS ...
Page 426: ...GEK 113285A G650 Generator Protection Control System A 31 APPENDIX A A 1 LOGIC OPERANDS A ...
Page 427: ...A 32 G650 Generator Protection Control System GEK 113285A A 1 LOGIC OPERANDS APPENDIXA A ...
Page 587: ...C 22 G650 Generator Protection Control System GEK 113285A C 8 ANALOG INPUTS APPENDIXC C ...
Page 639: ...G 2 G650 Generator Protection Control System GEK 113285A G 1 GE MULTILIN WARRANTY APPENDIXG G ...