5-4
G650 Generator Protection & Control System
GEK-113285A
5.2 PRODUCT SETUP
5 SETTINGS
5
5.2.1.4 DNP3 SLAVE
Physical port, Slave Address for DNP, IP Addresses for Masters, TCP/UDP Port, Unsolicited Response parameters, Analog
scale factors and deadbands, message fragment size, Binary input block. For more detailed information go to appendix C
in this manual.
Table 5–5: DNP PROTOCOL SETTINGS
PRODUCT SETUP > COMMUNICATION SETTINGS >DNP3 SLAVE
DNP3 SLAVE 1 > DNP3 SLAVE 2 > DNP3 SLAVE 3
Name
Default Value
Step
Range
Physical Port
NONE
N/A
[COM1:COM2:NETWORK]
Address
255
1
[0 : 65534]
IP Addr Client1 Oct1
0
1
[0 : 255]
IP Addr Client1 Oct2
0
1
[0 : 255]
IP Addr Client1 Oct3
0
1
[0 : 255]
IP Addr Client1 Oct4
0
1
[0 : 255]
IP Addr Client2 Oct1
0
1
[0 : 255]
IP Addr Client2 Oct2
0
1
[0 : 255]
IP Addr Client2 Oct3
0
1
[0 : 255]
IP Addr Client2 Oct4
0
1
[0 : 255]
IP Addr Client3 Oct1
0
1
[0 : 255]
IP Addr Client3 Oct2
0
1
[0 : 255]
IP Addr Client3 Oct3
0
1
[0 : 255]
IP Addr Client3 Oct4
0
1
[0 : 255]
IP Addr Client4 Oct1
0
1
[0 : 255]
IP Addr Client4 Oct2
0
1
[0 : 255]
IP Addr Client4 Oct3
0
1
[0 : 255]
IP Addr Client4 Oct4
0
1
[0 : 255]
IP Addr Client5 Oct1
0
1
[0 : 255]
IP Addr Client5 Oct2
0
1
[0 : 255]
IP Addr Client5 Oct3
0
1
[0 : 255]
IP Addr Client5 Oct4
0
1
[0 : 255]
TCP/UDP Port
20000
1
[0 : 65535]
Unsol Resp Function
DISABLED
N/A
[DISABLED – ENABLED]
Unsol Resp TimeOut
5
1
[0 : 60]
Unsol Resp Max Ret
10
1
[0 : 255]
Unsol Resp Dest Adr
200
1
[0 : 65535]
Current Scale Factor
1
N/A
[0.00001-0.0001-0.001-0.01-0.1-1-10-100-1000]
Voltage Scale Factor
1
N/A
[0.00001-0.0001-0.001-0.01-0.1-1-10-100-1000]
Power Scale Factor
1
N/A
[0.00001-0.0001-0.001-0.01-0.1-1-10-100-1000]
Energy Scale Factor
1
N/A
[0.00001-0.0001-0.001-0.01-0.1-1-10-100-1000]
Other Scale Factor
1
N/A
[0.00001-0.0001-0.001-0.01-0.1-1-10-100-1000]
Current Deadband
30000
1
[0 : 65535]
Voltage Deadband
30000
1
[0 : 65535]
Power Deadband
30000
1
[0 : 65535]
Energy Deadband
30000
1
[0 : 65535]
Other Deadband
30000
1
[0 : 65535]
Msg Fragment Size
240
1
[30 : 2048]
Binary Input Block 1
CTL EVENTS 1-16
N/A
Binary Input Block 2
CTL EVENTS 17-32
N/A
Binary Input Block 3
CTL EVENTS 33-48
N/A
Binary Input Block 4
CTL EVENTS 49-64
N/A
Binary Input Block 5
CTL EVENTS 65-80
N/A
Summary of Contents for Multilin G650
Page 9: ...8 G650 Generator Protection Control System GEK 113285A TABLE OF CONTENTS ...
Page 426: ...GEK 113285A G650 Generator Protection Control System A 31 APPENDIX A A 1 LOGIC OPERANDS A ...
Page 427: ...A 32 G650 Generator Protection Control System GEK 113285A A 1 LOGIC OPERANDS APPENDIXA A ...
Page 587: ...C 22 G650 Generator Protection Control System GEK 113285A C 8 ANALOG INPUTS APPENDIXC C ...
Page 639: ...G 2 G650 Generator Protection Control System GEK 113285A G 1 GE MULTILIN WARRANTY APPENDIXG G ...