GEK-113285A
G650 Generator Protection & Control System
C-9
APPENDIX C
C.3 IMPLEMENTATION TABLE
C
c) IMPLEMENTATION TABLE (SHEET 3 OUT OF 3)
Note 1: A default variation refers to the variation responded when variation 0 is requested and/or in class 0, 1, 2, or 3 scans.
Note 2: For static (non-change-event) objects, qualifiers 17 or 28 are only responded when a request is sent with qualifiers 17 or 28,
respectively. Otherwise, static object requests sent with qualifiers 00, 01, 06, 07, or 08, will be responded with qualifiers 00 or 01
(for change-event objects, qualifiers 17 or 28 are always responded).
Note 3: Cold restarts are implemented the same as warm restarts – The G650 is not restarted, but the DNP process is restarted.
OBJECT
REQUEST
RESPONSE
Object
No.
Variation
No.
Description
Function Codes
(dec)
Qualifier Codes
(hex)
Function Codes Qualifier Codes
(hex)
34
2
32-Bit Analog Input Reporting
Deadband
See Note 1
2
(write)
00,01
(start-stop)
07,08
(limited qty)
17,28
(index)
50
0
Time and Date - All Variations
1
(read)
00,01
(start-stop)
06
(no range, or all)
07,08
(limited qty)
17,28
(index)
129
(response)
00,01
(start-
stop)
17,28
(index)
See Note 2
50
1
Time and Date
See Note 1
1
(read)
2
(write)
00,01
(start-stop)
06
(no range, or all)
07
(limited qty=1)
08
(limited qty)
17,28
(index)
129
(response)
00,01
(start-
stop)
17,28
(index)
See Note 2
52
2
Time Delay Fine
1
(read)
2
(write)
129
(response)
07
(limited qty)
quantity=1
60
0
Class 0, 1, 2, and 3 Data
1
(read)
20
(enable unsol)
21
(disable unsol)
22
(assign class)
06
(no range, or all)
60
1
Class 0 Data
06
(no range, or all)
60
2
Class 1 Data
1
(read)
20
(enable unsol)
21
(disable unsol)
22
(assign class)
06
(no range, or all)
07,08
(limited qty)
60
3
Class 2 Data
1
(read)
20
(enable unsol)
21
(disable unsol)
22
(assign class)
06
(no range, or all)
07,08
(limited qty)
60
4
Class 3 Data
1
(read)
20
(enable unsol)
21
(disable unsol)
22
(assign class)
06
(no range, or all)
07,08
(limited qty)
80
1
Internal Indications
2
(write)
00
(start-stop)
(index must =7)
No Object (function code only)
See Note 3
13
(cold restart)
No Object (function code only)
14
(warm restart)
No Object (function code only)
23
(delay meas.)
Summary of Contents for Multilin G650
Page 9: ...8 G650 Generator Protection Control System GEK 113285A TABLE OF CONTENTS ...
Page 426: ...GEK 113285A G650 Generator Protection Control System A 31 APPENDIX A A 1 LOGIC OPERANDS A ...
Page 427: ...A 32 G650 Generator Protection Control System GEK 113285A A 1 LOGIC OPERANDS APPENDIXA A ...
Page 587: ...C 22 G650 Generator Protection Control System GEK 113285A C 8 ANALOG INPUTS APPENDIXC C ...
Page 639: ...G 2 G650 Generator Protection Control System GEK 113285A G 1 GE MULTILIN WARRANTY APPENDIXG G ...