GEK-113285A
G650 Generator Protection & Control System
F-13
APPENDIX F
F.1 FACTORY DEFAULT SETTINGS
F
SETPOINT > PROTECTION ELEMENTS >VOLTAGE ELEMENTS>AUXILIARY OV
AUXILIARY OV 1> AUXILIARY OV 2 > AUXILIARY OV 3
SETTING DESCRIPTION
NAME
DEFAULT VALUE
STEP
RANGE
USER
VALUE
Function permission
Function
DISABLED
N/A
[DISABLED – ENABLED]
Pickup Level
Pickup Level
10
1 V
[3 : 500]
Trip Time
Trip Delay
10.00
0.01 s
[0.00 : 900.00]]
Reset Time
Reset Delay
0.00
0.01 s
[0.00 : 900.00]
Snapshot Event generation
Snapshot Events
ENABLED
N/A
[DISABLED – ENABLED]
SETPOINT > PROTECTION ELEMENTS >VOLTAGE ELEMENTS>AUXILIARY UV
AUXILIARY UV 1> AUXILIARY UV 2 > AUXILIARY UV 3
SETTING DESCRIPTION
NAME
DEFAULT VALUE
STEP
RANGE
USER
VALUE
Function permission
Function
DISABLED
N/A
[DISABLED – ENABLED]
Pickup Level
Pickup Level
10
1 V
[3 : 500]
Curve shape
Curve
DEFINITE TIME
N/A
[DEFINITE TIME –
INVERSE TIME]
Time Dial
Delay
10.00
0.01 s
[0.00 : 900.00]
Snapshot Event generation
Snapshot Events
ENABLED
N/A
[DISABLED – ENABLED]
SETPOINT > PROTECTION ELEMENTS >VOLTAGE ELEMENTS>VOLTS/HERTZ (ENHANCED MODELS ONLY)
VOLTS/HERTZ 1> VOLTS/HERTZ 2 > VOLTS/HERTZ 3
SETTING DESCRIPTION
NAME
DEFAULT VALUE
STEP
RANGE
USER
VALUE
Function permission
Function
DISABLED
N/A
[DISABLED – ENABLED]
V/Hz Source for element calculations
V/Hz Source
PHASES
N/A
[PHASES – AUX
VOLTAGE]
V/Hz Minimum operating Voltage
V/Hz Minimum Voltage 40.00
0.01 V
[30.00 : 500.00]
V/Hz Pickup Level
V/Hz Pickup Level
1.00
0.01 pu
[0.80 : 4.00]
V/Hz Curve
V/Hz Curve
DEFINITE TIME
[DEFINITE TIME-CURVE
A-CURVE B – CURVE C]
V/Hz TD Multiplier
V/Hz TD Multiplier
1.00
0.01
[0.05 : 600.00]
V/Hz Reset Delay
V/Hz Reset Delay
1.0
0.1 s
[0.0 : 900.0]
Snapshot Event generation
Snapshot Events
ENABLED
N/A
[DISABLED – ENABLED]
SETPOINT > PROTECTION ELEMENTS >VOLTAGE ELEMENTS>GROUND OV
GROUND OV 1> GROUND OV 2 > GROUND OV 3
SETTING DESCRIPTION
NAME
DEFAULT VALUE
STEP
RANGE
USER
VALUE
Function permission
Function
DISABLED
N/A
[DISABLED – ENABLED]
Pickup level
Pickup Level
10
1 V
[3 – 500]
Trip Time
Trip Delay
10.00
0.01 s
[0.00 – 900.00]
Reset Time
Reset Delay
0.00
0.01 s
[0.00 – 900.00]
Snapshot event generation
Snapshot Events
ENABLED
N/A
[DISABLED – ENABLED]
Summary of Contents for Multilin G650
Page 9: ...8 G650 Generator Protection Control System GEK 113285A TABLE OF CONTENTS ...
Page 426: ...GEK 113285A G650 Generator Protection Control System A 31 APPENDIX A A 1 LOGIC OPERANDS A ...
Page 427: ...A 32 G650 Generator Protection Control System GEK 113285A A 1 LOGIC OPERANDS APPENDIXA A ...
Page 587: ...C 22 G650 Generator Protection Control System GEK 113285A C 8 ANALOG INPUTS APPENDIXC C ...
Page 639: ...G 2 G650 Generator Protection Control System GEK 113285A G 1 GE MULTILIN WARRANTY APPENDIXG G ...