GEK-113285A
G650 Generator Protection & Control System
5-69
5 SETTINGS
5.4 PROTECTION ELEMENTS
5
The 1 pu value for V/Hz operation is the Nominal Voltage setting divided by the Nominal Frequency
setting adjusted in the
General Settings menu.
The characteristics of the inverse curves are shown below:
•
DEFINITE TIME: T (sec) = TD Multiplier.
•
INVERSE CURVE A:
where:
T = operating time
TDM = Time Delay Multiplier (sec)
V = fundamental value of voltage (pu)
F=frequency of voltage signal (pu)
Pickup= volts-per-hertz pickup setpoint (pu)
•
INVERSE CURVE B:
where:
T = operating time
TDM = Time Delay Multiplier (sec)
V = fundamental value of voltage (pu)
F=frequency of voltage signal (pu)
Pickup= volts-per-hertz pickup setpoint (pu)
•
INVERSE CURVE C:
where:
T = operating time
TDM = Time Delay Multiplier (sec)
V = fundamental value of voltage (pu)
F=frequency of voltage signal (pu)
Pickup= volts-per-hertz pickup setpoint (pu)
Pickup
F
whenV
Pickup
F
V
TDM
T
>
−
⎥
⎦
⎤
⎢
⎣
⎡
⎟
⎠
⎞
⎜
⎝
⎛
=
/
1
2
Pickup
F
whenV
Pickup
F
V
TDM
T
>
−
⎥
⎦
⎤
⎢
⎣
⎡
⎟
⎠
⎞
⎜
⎝
⎛
=
/
1
Pickup
F
whenV
Pickup
F
V
TDM
T
>
−
⎥
⎦
⎤
⎢
⎣
⎡
⎟
⎠
⎞
⎜
⎝
⎛
=
/
1
5
.
0
Summary of Contents for Multilin G650
Page 9: ...8 G650 Generator Protection Control System GEK 113285A TABLE OF CONTENTS ...
Page 426: ...GEK 113285A G650 Generator Protection Control System A 31 APPENDIX A A 1 LOGIC OPERANDS A ...
Page 427: ...A 32 G650 Generator Protection Control System GEK 113285A A 1 LOGIC OPERANDS APPENDIXA A ...
Page 587: ...C 22 G650 Generator Protection Control System GEK 113285A C 8 ANALOG INPUTS APPENDIXC C ...
Page 639: ...G 2 G650 Generator Protection Control System GEK 113285A G 1 GE MULTILIN WARRANTY APPENDIXG G ...