5-112
G650 Generator Protection & Control System
GEK-113285A
5.6 INPUTS/OUTPUTS
5 SETTINGS
5
b) WITHOUT SUPERVISION
This is a very frequent common case, and we must only wire the tripping circuit to terminals F35 and F36, leaving unused
terminals F34, F15, F16, F17, F18.
Figure 5–30: CIRCUIT WITHOUT TRIPPING CIRCUIT SUPERVISION (A6631F1)