GEK-113285A
G650 Generator Protection & Control System
B-133
APPENDIX B
B.7 MEMORY MAP
B
0x4412
PF Stg2 Trip Delay
F003
1
R/W
2
[0.2 , 300.0] s
0x4414
Snapshot Events
F012
1
R/W
1
0=DISABLED
1=ENABLED
0x441E
Confirmation address
W
1
Ajustes Limitador Factor de Potencia Grupo 3 - Pwr Factor Limiting 3 Settings(Enhanced models only)
0x441F
Function
F012
1
R/W
1
0=DISABLED
1=ENABLED
0x4420
PF Lead Stg1 Level
F003
1
R/W
2
[0.05 , 0.99]
0x4422
PF Lag Stg1 Level
F003
1
R/W
2
[0.05 , 0.99]
0x4424
PF Stg1 Trip Delay
F003
1
R/W
2
[0.2 , 300.0] s
0x4426
PF Lead Stg2 Level
F003
1
R/W
2
[0.05 , 0.99]
0x4428
PF Lag Stg2 Level
F003
1
R/W
2
[0.05 , 0.99]
0x442A
PF Stg2 Trip Delay
F003
1
R/W
2
[0.2 , 300.0] s
0x442C
Snapshot Events
F012
1
R/W
1
0=DISABLED
1=ENABLED
0x4436
Confirmation address
W
1
Ajustes Energización Accidental Grupo 1 - Accidental Energization 1 Settings
0x4437
Function
F012
1
R/W
1
0=DISABLED
1=ENABLED
0x4438
Accdnt Enrg Mode
F012
1
R/W
1
0=UV AND OFF-LINE
1=UV OR OFF-LINE
0x4439
Overcurrent pickup
F003
1
R/W
2
[0.00 , 160.00] A
0x443B
Ph Undervoltage pickup
F003
1
R/W
2
[0.00 , 500.00] V
0x443D
Snapshot Events
F012
1
R/W
1
0=DISABLED
1=ENABLED
0x4447
Confirmation address
W
1
Ajustes Energización Accidental Grupo 2 - Accidental Energization 2 Settings
0x4448
Function
F012
1
R/W
1
0=DISABLED
1=ENABLED
0x4449
Accdnt Enrg Mode
F012
1
R/W
1
0=UV AND OFF-LINE
1=UV OR OFF-LINE
0x444A
Overcurrent pickup
F003
1
R/W
2
[0.00 , 160.00] A
0x444C
Ph Undervoltage pickup
F003
1
R/W
2
[0.00 , 500.00] V
0x444E
Snapshot Events
F012
1
R/W
1
0=DISABLED
1=ENABLED
0x4458
Confirmation address
W
1
Ajustes Energización Accidental Grupo 3 - Accidental Energization 3 Settings
0x4459
Function
F012
1
R/W
1
0=DISABLED
1=ENABLED
0x445A
Accdnt Enrg Mode
F012
1
R/W
1
0=UV AND OFF-LINE
1=UV OR OFF-LINE
0x445B
Overcurrent pickup
F003
1
R/W
2
[0.00 , 160.00] A
0x445D
Ph Undervoltage pickup
F003
1
R/W
2
[0.00 , 500.00] V
0x445F
Snapshot Events
F012
1
R/W
1
0=DISABLED
1=ENABLED
0x4469
Confirmation address
W
1
Ajustes Sobretensión Tierra Grupo 1 - Ground OV 1 Settings
0x446A
Function
F012
1
R/W
1
0=DISABLED
1=ENABLED
0x446B
Pickup Level
F003
1
R/W
2
[3 , 500] V
0x446D
Trip Delay
F003
1
R/W
2
[0.00 , 900.00] s
0x446F
Reset Delay
F003
1
R/W
2
[0.00 , 900.00] s
0x4471
Snapshot Events
F012
1
R/W
1
0=DISABLED
ADDRESS BIT
NAME
FORMAT
STEP MODE LENGTH
MISCELLANEOUS
Summary of Contents for Multilin G650
Page 9: ...8 G650 Generator Protection Control System GEK 113285A TABLE OF CONTENTS ...
Page 426: ...GEK 113285A G650 Generator Protection Control System A 31 APPENDIX A A 1 LOGIC OPERANDS A ...
Page 427: ...A 32 G650 Generator Protection Control System GEK 113285A A 1 LOGIC OPERANDS APPENDIXA A ...
Page 587: ...C 22 G650 Generator Protection Control System GEK 113285A C 8 ANALOG INPUTS APPENDIXC C ...
Page 639: ...G 2 G650 Generator Protection Control System GEK 113285A G 1 GE MULTILIN WARRANTY APPENDIXG G ...