B-130
G650 Generator Protection & Control System
GEK-113285A
B.7 MEMORY MAP
APPENDIX B
B
2=CURVE B
3=CURVE C
0x42FE
V/Hz TD Multiplier
F003
1
R/W
2
[0.05 , 600.00]
0x4300
V/Hz Reset Delay
F003
1
R/W
2
[0.0 , 900.0] s
0x4302
Snapshot Events
F012
1
R/W
1
0=DISABLED
1=ENABLED
0x430C
Confirmation address
W
1
Ajustes Voltios/ Hercios Grupo 3 - Volts per Hertz 3 Settings(Enhanced models only)
0x430D
Function
F012
1
R/W
1
0=DISABLED
1=ENABLED
0x430E
V/Hz Source
F012
1
R/W
1
0=PHASES
1=AUX VOLTAGE
0x430F
V/Hz Minimum Voltage
F003
1
R/W
2
[30.00 , 500.00] V
0x4311
V/Hz Pickup Level
F003
1
R/W
2
[0.80 , 4.00] pu
0x4313
V/Hz Curve
F012
1
R/W
1
0=DEFINITE TIME
1=CURVE A
2=CURVE B
3=CURVE C
0x4314
V/Hz TD Multiplier
F003
1
R/W
2
[0.05 , 600.00]
0x4316
V/Hz Reset Delay
F003
1
R/W
2
[0.0 , 900.0] s
0x4318
Snapshot Events
F012
1
R/W
1
0=DISABLED
1=ENABLED
0x4322
Confirmation address
W
1
Ajustes Pérdida de Excitación Grupo 1 - Loss of Excitation 1 Settings
0x4323
Function
F012
1
R/W
1
0=DISABLED
1=ENABLED
0x4324
Stage 1 Center
F003
1
R/W
2
[0.10 , 300.00] Ohm
0x4326
Stage 1 Radius
F003
1
R/W
2
[0.10 , 300.00] Ohm
0x4328
Stage 1 UV Supv
F012
1
R/W
1
0=DISABLED
1=ENABLED
0x4329
Stage 1 Trip Delay
F003
1
R/W
2
[0.00 , 65.54] s
0x432B
Stage 2 Center
F003
1
R/W
2
[0.10 , 300.00] Ohm
0x432D
Stage 2 Radius
F003
1
R/W
2
[0.10 , 300.00] Ohm
0x432F
Stage 2 UV Supv
F012
1
R/W
1
0=DISABLED
1=ENABLED
0x4330
Stage 2 Trip Delay
F003
1
R/W
2
[0.00 , 65.54] s
0x4332
UV Supv Level
F003
1
R/W
2
[0.0 , 500.0] V
0x4334
Snapshot Events
F012
1
R/W
1
0=DISABLED
1=ENABLED
0x433E
Confirmation address
W
1
Ajustes Pérdida de Excitación Grupo 2 - Loss of Excitation 2 Settings
0x433F
Function
F012
1
R/W
1
0=DISABLED
1=ENABLED
0x4340
Stage 1 Center
F003
1
R/W
2
[0.10 , 300.00] Ohm
0x4342
Stage 1 Radius
F003
1
R/W
2
[0.10 , 300.00] Ohm
0x4344
Stage 1 UV Supv
F012
1
R/W
1
0=DISABLED
1=ENABLED
0x4345
Stage 1 Trip Delay
F003
1
R/W
2
[0.00 , 65.54] s
0x4347
Stage 2 Center
F003
1
R/W
2
[0.10 , 300.00] Ohm
0x4349
Stage 2 Radius
F003
1
R/W
2
[0.10 , 300.00] Ohm
0x434B
Stage 2 UV Supv
F012
1
R/W
1
0=DISABLED
1=ENABLED
0x434C
Stage 2 Trip Delay
F003
1
R/W
2
[0.00 , 65.54] s
ADDRESS BIT
NAME
FORMAT
STEP MODE LENGTH
MISCELLANEOUS
Summary of Contents for Multilin G650
Page 9: ...8 G650 Generator Protection Control System GEK 113285A TABLE OF CONTENTS ...
Page 426: ...GEK 113285A G650 Generator Protection Control System A 31 APPENDIX A A 1 LOGIC OPERANDS A ...
Page 427: ...A 32 G650 Generator Protection Control System GEK 113285A A 1 LOGIC OPERANDS APPENDIXA A ...
Page 587: ...C 22 G650 Generator Protection Control System GEK 113285A C 8 ANALOG INPUTS APPENDIXC C ...
Page 639: ...G 2 G650 Generator Protection Control System GEK 113285A G 1 GE MULTILIN WARRANTY APPENDIXG G ...