5.9 LOGIC CONFIGURATION (PLC EDITOR)
5 SETTINGS
5
5.9.2 THEORY OF OPERATION
5.9.2.1 DESCRIPTION
As already mentioned in the introduction, this tool uses FBD mode of IEC 61131-3 standard. For this purpose we have
defined a series of basic operations with illustrations below.
The basic operations available in PLC Editor are located in the tool bar of the application and are as follows:
Table 5–114: PLC EDITOR BASIC OPERATION IN
G650
PLC EDITOR BASIC OPERATION
ICONS IN SCREEN DESCRIPTION
INPUT TO LOGIC: Selection of the digital input to the logic. (All available internal status can be used as logic
inputs)
OUTPUT FROM LOGIC: Virtual output built with internal logic. (Up to 512)
LIBRARY: Possibility to build blocks of logic in a simple graphic object. OR and AND from 3 to 8 inputs are provided
as libraries.
AND of two digital inputs.
OR of two digital inputs.
NOT of a digital input.
NAND of two digital inputs.
XOR of two digital inputs.
SR: Latch (set-reset): reset dominant.
ONS: signal to pulse an logic input to a signal of one scan cycle length.
TIMER: timer signal with set, reset and mask for timing.
TEXT LABEL: text to customize the logic configuration file.
Flip-Flop D: signal that maintains the actual value frozen during a PLC cycle
MASK: Time mask to be used in timing operations.
Summary of Contents for Multilin G650
Page 9: ...8 G650 Generator Protection Control System GEK 113285A TABLE OF CONTENTS ...
Page 426: ...GEK 113285A G650 Generator Protection Control System A 31 APPENDIX A A 1 LOGIC OPERANDS A ...
Page 427: ...A 32 G650 Generator Protection Control System GEK 113285A A 1 LOGIC OPERANDS APPENDIXA A ...
Page 587: ...C 22 G650 Generator Protection Control System GEK 113285A C 8 ANALOG INPUTS APPENDIXC C ...
Page 639: ...G 2 G650 Generator Protection Control System GEK 113285A G 1 GE MULTILIN WARRANTY APPENDIXG G ...