5-30
G60 Generator Protection System
GE Multilin
5.2 PRODUCT SETUP
5 SETTINGS
5
Multiple LANS, No Redundancy
The following topology provides local configuration/monitoring through EnerVista software on LAN1, to which port 1 (P1) is
connected, access to the public network on LAN2, to which port 2 (P2) is connected and communications with SCADA on
LAN3, to which port 3 (P3) is connected. There is no redundancy.
Figure 5–6: MULTIPLE LANS, NO REDUNDANCY
d) NETWORK
As outlined in the previous section, when using more than one Ethernet port, configure each to belong to a different net-
work or subnet using the IP addresses and mask. Configure the network IP and subnet settings before configuring the rout-
ing settings.
PATH: SETTINGS
PRODUCT SETUP
COMMUNICATIONS
NETWORK 1(3)
NETWORK PORT 1
PRT1 IP ADDRESS:
127.0.0.1
Range: Standard IPV4 address format
MESSAGE
PRT1 SUBNET IP MASK:
255.0.0.0
Range: Standard IPV4 address format
MESSAGE
PRT1 GOOSE ENABLED:
Enabled
Range: Enabled, Disabled
NETWORK PORT 2
PRT2 IP ADDRESS:
127.0.0.1
Range: Standard IPV4 address format
MESSAGE
PRT2 SUBNET IP MASK:
255.0.0.0
Range: Standard IPV4 address format
MESSAGE
PRT2 REDUNDANCY:
None
Range: None, Failover, PRP
None, Failover (if no PRP license)
MESSAGE
PRT2 PRP MCST ADDR:
01-15-4E-00-01-00
Range: 01-15-4E-00-01-00 to 01-15-4E-00-01-FF
MESSAGE
PRT2 GOOSE ENABLED:
Enabled
Range: Enabled, Disabled
EnerVista Software
ML3000
Public Network
SCADA
UR
P1
IP1/
MAC1
P2
IP2/
MAC2
ML3000
ML3000
LAN1
LAN2
LAN3
P3
IP3/
MAC3
859710A2.vsd
Summary of Contents for Multilin g60
Page 10: ...x G60 Generator Protection System GE Multilin TABLE OF CONTENTS INDEX ...
Page 32: ...1 22 G60 Generator Protection System GE Multilin 1 5 USING THE RELAY 1 GETTING STARTED 1 ...
Page 160: ...4 30 G60 Generator Protection System GE Multilin 4 3 FACEPLATE INTERFACE 4 HUMAN INTERFACES 4 ...
Page 486: ...5 326 G60 Generator Protection System GE Multilin 5 10 TESTING 5 SETTINGS 5 ...
Page 518: ...6 32 G60 Generator Protection System GE Multilin 6 5 PRODUCT INFORMATION 6 ACTUAL VALUES 6 ...
Page 532: ...7 14 G60 Generator Protection System GE Multilin 7 2 TARGETS 7 COMMANDS AND TARGETS 7 ...
Page 748: ...D 10 G60 Generator Protection System GE Multilin D 1 IEC 60870 5 104 APPENDIX D D ...
Page 760: ...E 12 G60 Generator Protection System GE Multilin E 2 DNP POINT LISTS APPENDIX E E ...