B-50
G60 Generator Protection System
GE Multilin
B.4 MEMORY MAPPING
APPENDIX B
B
8D86
...Repeated for Digital Element 42
8D9C
...Repeated for Digital Element 43
8DB2
...Repeated for Digital Element 44
8DC8
...Repeated for Digital Element 45
8DDE
...Repeated for Digital Element 46
8DF4
...Repeated for Digital Element 47
8E0A
...Repeated for Digital Element 48
Trip Bus (Read/Write Setting) (6 modules)
8ED0
Trip Bus 1 Function
0 to 1
---
1
F102
0 (Disabled)
8ED1
Trip Bus 1 Block
0 to 4294967295
---
1
F300
0
8ED3
Trip Bus 1 Pickup Delay
0 to 600
s
0.01
F001
0
8ED4
Trip Bus 1 Reset Delay
0 to 600
s
0.01
F001
0
8ED5
Trip Bus 1 Input (16 items)
0 to 4294967295
---
1
F300
0
8EF5
Trip Bus 1 Latching
0 to 1
---
1
F102
0 (Disabled)
8EF6
Trip Bus 1 Reset
0 to 4294967295
---
1
F300
0
8EF8
Trip Bus 1 Target
0 to 2
---
1
F109
0 (Self-reset)
8EF9
Trip Bus 1 Events
0 to 1
---
1
F102
0 (Disabled)
8EFA
Reserved (8 items)
0 to 1
---
1
F001
0
8F02
...Repeated for Trip Bus 2
8F34
...Repeated for Trip Bus 3
8F66
...Repeated for Trip Bus 4
8F98
...Repeated for Trip Bus 5
8FCA
...Repeated for Trip Bus 6
FlexElement (Read/Write Setting) (16 modules)
9000
FlexElement 1 Function
0 to 1
---
1
F102
0 (Disabled)
9001
FlexElement 1 Name
---
---
---
F206
“FxE 1”
9004
FlexElement 1 InputP
0 to 65535
---
1
F600
0
9005
FlexElement 1 InputM
0 to 65535
---
1
F600
0
9006
FlexElement 1 Compare
0 to 1
---
1
F516
0 (LEVEL)
9007
FlexElement 1 Input
0 to 1
---
1
F515
0 (SIGNED)
9008
FlexElement 1 Direction
0 to 1
---
1
F517
0 (OVER)
9009
FlexElement 1 Hysteresis
0.1 to 50
%
0.1
F001
30
900A
FlexElement 1 Pickup
-90 to 90
pu
0.001
F004
1000
900C
FlexElement 1 DeltaT Units
0 to 2
---
1
F518
0 (Milliseconds)
900D
FlexElement 1 DeltaT
20 to 86400
---
1
F003
20
900F
FlexElement 1 Pickup Delay
0 to 65.535
s
0.001
F001
0
9010
FlexElement 1 Reset Delay
0 to 65.535
s
0.001
F001
0
9011
FlexElement 1 Block
0 to 4294967295
---
1
F300
0
9013
FlexElement 1 Target
0 to 2
---
1
F109
0 (Self-reset)
9014
FlexElement 1 Events
0 to 1
---
1
F102
0 (Disabled)
9015
...Repeated for FlexElement 2
902A
...Repeated for FlexElement 3
903F
...Repeated for FlexElement 4
9054
...Repeated for FlexElement 5
9069
...Repeated for FlexElement 6
907E
...Repeated for FlexElement 7
9093
...Repeated for FlexElement 8
90A8
...Repeated for FlexElement 9
90BD
...Repeated for FlexElement 10
90D2
...Repeated for FlexElement 11
90E7
...Repeated for FlexElement 12
90FC
...Repeated for FlexElement 13
9111
...Repeated for FlexElement 14
9126
...Repeated for FlexElement 15
Table B–10: MODBUS MEMORY MAP (Sheet 42 of 68)
ADDR
REGISTER NAME
RANGE
UNITS
STEP
FORMAT
DEFAULT
Summary of Contents for Multilin g60
Page 10: ...x G60 Generator Protection System GE Multilin TABLE OF CONTENTS INDEX ...
Page 32: ...1 22 G60 Generator Protection System GE Multilin 1 5 USING THE RELAY 1 GETTING STARTED 1 ...
Page 160: ...4 30 G60 Generator Protection System GE Multilin 4 3 FACEPLATE INTERFACE 4 HUMAN INTERFACES 4 ...
Page 486: ...5 326 G60 Generator Protection System GE Multilin 5 10 TESTING 5 SETTINGS 5 ...
Page 518: ...6 32 G60 Generator Protection System GE Multilin 6 5 PRODUCT INFORMATION 6 ACTUAL VALUES 6 ...
Page 532: ...7 14 G60 Generator Protection System GE Multilin 7 2 TARGETS 7 COMMANDS AND TARGETS 7 ...
Page 748: ...D 10 G60 Generator Protection System GE Multilin D 1 IEC 60870 5 104 APPENDIX D D ...
Page 760: ...E 12 G60 Generator Protection System GE Multilin E 2 DNP POINT LISTS APPENDIX E E ...