B-42
G60 Generator Protection System
GE Multilin
B.4 MEMORY MAPPING
APPENDIX B
B
7202
Phase Directional Overcurrent 1 Block
0 to 4294967295
---
1
F300
0
7204
Phase Directional Overcurrent 1 ECA
0 to 359
degrees
1
F001
30
7205
Phase Directional Overcurrent 1 Pol V Threshold
0 to 3
pu
0.001
F001
700
7206
Phase Directional Overcurrent 1 Block Overcurrent
0 to 1
---
1
F126
0 (No)
7207
Phase Directional Overcurrent 1 Target
0 to 2
---
1
F109
0 (Self-reset)
7208
Phase Directional Overcurrent 1 Events
0 to 1
---
1
F102
0 (Disabled)
7209
Reserved (8 items)
0 to 1
---
1
F001
0
Neutral Directional Overcurrent (Read/Write Grouped Setting) (2 modules)
7230
Neutral Directional Overcurrent 1 Function
0 to 1
---
1
F102
0 (Disabled)
7231
Neutral Directional Overcurrent 1 Source
0 to 5
---
1
F167
0 (SRC 1)
7232
Neutral Directional Overcurrent 1 Polarizing
0 to 2
---
1
F230
0 (Voltage)
7233
Neutral Directional Overcurrent 1 Forward ECA
-90 to 90
° Lag
1
F002
75
7234
Neutral Directional Overcurrent 1 Forward Limit Angle
40 to 90
degrees
1
F001
90
7235
Neutral Directional Overcurrent 1 Forward Pickup
0.006 to 30
pu
0.001
F001
50
7236
Neutral Directional Overcurrent 1 Reverse Limit Angle
40 to 90
degrees
1
F001
90
7237
Neutral Directional Overcurrent 1 Reverse Pickup
0.006 to 30
pu
0.001
F001
50
7238
Neutral Directional Overcurrent 1 Target
0 to 2
---
1
F109
0 (Self-reset)
7239
Neutral Directional Overcurrent 1 Block
0 to 4294967295
---
1
F300
0
723B
Neutral Directional Overcurrent 1 Events
0 to 1
---
1
F102
0 (Disabled)
723C
Neutral Directional Overcurrent 1 Polarizing Voltage
0 to 1
---
1
F231
0 (Calculated V0)
723D
Neutral Directional Overcurrent 1 Op Current
0 to 1
---
1
F196
0 (Calculated 3I0)
723E
Neutral Directional Overcurrent 1 Offset
0 to 250
ohms
0.01
F001
0
723F
Neutral Directional Overcurrent 1 Pos Seq Restraint
0 to 0.5
---
0.001
F001
63
7240
Reserved
0 to 1
---
1
F001
0
7241
...Repeated for Neutral Directional Overcurrent 2
Negative-Sequence Directional Overcurrent (Read/Write Grouped Settings) (2 modules)
7260
Negative Sequence Directional Overcurrent 1 Function
0 to 1
---
1
F102
0 (Disabled)
7261
Negative Sequence Directional Overcurrent 1 Source
0 to 5
---
1
F167
0 (SRC 1)
7262
Negative Sequence Directional Overcurrent 1 Type
0 to 1
---
1
F179
0 (Neg Sequence)
7263
Neg Sequence Directional Overcurrent 1 Forward ECA
0 to 90
° Lag
1
F002
75
7264
Neg Seq Directional Overcurrent 1 Forward Limit Angle
40 to 90
degrees
1
F001
90
7265
Neg Sequence Directional Overcurrent 1 Forward Pickup
0.015 to 30
pu
0.005
F001
50
7266
Neg Seq Directional Overcurrent 1 Reverse Limit Angle
40 to 90
degrees
1
F001
90
7267
Neg Sequence Directional Overcurrent 1 Reverse Pickup
0.015 to 30
pu
0.005
F001
50
7268
Negative Sequence Directional Overcurrent 1 Target
0 to 2
---
1
F109
0 (Self-reset)
7269
Negative Sequence Directional Overcurrent 1 Block
0 to 4294967295
---
1
F300
0
726B
Negative Sequence Directional Overcurrent 1 Events
0 to 1
---
1
F102
0 (Disabled)
726C
Negative Sequence Directional Overcurrent 1 Offset
0 to 250
ohms
0.01
F001
0
726D
Neg Seq Directional Overcurrent 1 Pos Seq Restraint
0 to 0.5
---
0.001
F001
63
726E
Reserved (3 items)
0 to 1
---
1
F001
0
7271
...Repeated for Neg Seq Directional Overcurrent 2
Disconnect (Breaker) Switch (Read/Write Setting) (16 modules)
74A0
Disconnect Switch 1 Function
0 to 1
---
1
F102
0 (Disabled)
74A1
Disconnect Switch 1 Name
---
---
---
F206
“SW 1"
74A4
Disconnect Switch 1 Mode
0 to 1
---
1
F157
0 (3-Pole)
74A5
Disconnect Switch 1 Open
0 to 4294967295
---
1
F300
0
74A7
Disconnect Switch 1 Block Open
0 to 4294967295
---
1
F300
0
74A9
Disconnect Switch 1 Close
0 to 4294967295
---
1
F300
0
74AB
Disconnect Switch 1 Block Close
0 to 4294967295
---
1
F300
0
74AD
Disconnect Switch 1 Phase A / Three-pole Closed
0 to 4294967295
---
1
F300
0
74AF
Disconnect Switch 1 Phase A / Three-pole Opened
0 to 4294967295
---
1
F300
0
74B1
Disconnect Switch 1 Phase B Closed
0 to 4294967295
---
1
F300
0
74B3
Disconnect Switch 1 Phase B Opened
0 to 4294967295
---
1
F300
0
Table B–10: MODBUS MEMORY MAP (Sheet 34 of 68)
ADDR
REGISTER NAME
RANGE
UNITS
STEP
FORMAT
DEFAULT
Summary of Contents for Multilin g60
Page 10: ...x G60 Generator Protection System GE Multilin TABLE OF CONTENTS INDEX ...
Page 32: ...1 22 G60 Generator Protection System GE Multilin 1 5 USING THE RELAY 1 GETTING STARTED 1 ...
Page 160: ...4 30 G60 Generator Protection System GE Multilin 4 3 FACEPLATE INTERFACE 4 HUMAN INTERFACES 4 ...
Page 486: ...5 326 G60 Generator Protection System GE Multilin 5 10 TESTING 5 SETTINGS 5 ...
Page 518: ...6 32 G60 Generator Protection System GE Multilin 6 5 PRODUCT INFORMATION 6 ACTUAL VALUES 6 ...
Page 532: ...7 14 G60 Generator Protection System GE Multilin 7 2 TARGETS 7 COMMANDS AND TARGETS 7 ...
Page 748: ...D 10 G60 Generator Protection System GE Multilin D 1 IEC 60870 5 104 APPENDIX D D ...
Page 760: ...E 12 G60 Generator Protection System GE Multilin E 2 DNP POINT LISTS APPENDIX E E ...