3-24
G60 Generator Protection System
GE Multilin
3.2 WIRING
3 HARDWARE
3
Figure 3–24: RTD CONNECTIONS
Three-wire shielded cable
RTD terminals
Maximum total lead resistance:
25 ohms for Platinum RTDs
Route cable in separate conduit from
current carrying conductors
RTD
859736A1.CDR
RTD terminals
RTD
RTD
For RTD
RTD
SURGE
~1
~1 & ~2
~2
~8b
~1a
~1b
~2a
Hot
Hot
Return
Comp
Comp ~2c
~1c