GE Multilin
G60 Generator Protection System
5-79
5 SETTINGS
5.2 PRODUCT SETUP
5
Figure 5–16: USER-PROGRAMMABLE PUSHBUTTON LOGIC (Sheet 2 of 2)
User-programmable pushbuttons require a type HP or HQ faceplate. If an HP or HQ type faceplate was ordered
separately, the relay order code must be changed to indicate the correct faceplate option. This can be done via
EnerVista UR Setup with the
Maintenance > Enable Pushbutton
command.
Pushbutton 1
LED
Instantaneous
reset *
OR
1. If pushbutton 1 LED control is set to off.
2. If pushbutton 1 LED control is not set to off.
PUSHBUTTON 1 LED LOGIC
OR
AND
AND
SETTING
= Disabled
= High Priority
Message Priority
= Normal
FLEXLOGIC OPERAND
PUSHBUTTON 1 ON
Pushbutton 1
LED
SETTING
= any FlexLogic operand
PUSHBTN 1 LED CTL
AND
SETTING
Flash Message Time
T
RST
0
PUSHBUTTON ON
LATCHED
LATCHED/SELF-RESET
AND
From user-programmable
pushbuttons logic
sheet 1, 842021A3
FLEXLOGIC OPERAND
PUSHBUTTON 1 ON
FLEXLOGIC OPERAND
PUSHBUTTON 1 OFF
SETTING
T
RST
0
Instantaneous
reset *
LCD MESSAGE
ENGAGE MESSAGE
SETTINGS
= XXXXXXXXXX
Top Text
= XXXXXXXXXX
On Text
The message is temporarily removed if
any keypad button is pressed. Ten (10)
seconds of keypad inactivity restores
the message.
LCD MESSAGE
ENGAGE MESSAGE
SETTINGS
= XXXXXXXXXX
Top Text
= XXXXXXXXXX
On Text
Instantaneous reset will be executed if any
front panel button is pressed or any new
target or message becomes active.
842024A2.CDR
OR
FLEXLOGIC OPERAND
PUSHBUTTON 1 ON
PUSHBUTTON 2 ON
PUSHBUTTON 3 ON
PUSHBUTTON 16 ON
FLEXLOGIC OPERAND
ANY PB ON
The enhanced front panel has 16 operands;
the standard front panel has 12
Flash Message Time
NOTE
Summary of Contents for Multilin g60
Page 10: ...x G60 Generator Protection System GE Multilin TABLE OF CONTENTS INDEX ...
Page 32: ...1 22 G60 Generator Protection System GE Multilin 1 5 USING THE RELAY 1 GETTING STARTED 1 ...
Page 160: ...4 30 G60 Generator Protection System GE Multilin 4 3 FACEPLATE INTERFACE 4 HUMAN INTERFACES 4 ...
Page 486: ...5 326 G60 Generator Protection System GE Multilin 5 10 TESTING 5 SETTINGS 5 ...
Page 518: ...6 32 G60 Generator Protection System GE Multilin 6 5 PRODUCT INFORMATION 6 ACTUAL VALUES 6 ...
Page 532: ...7 14 G60 Generator Protection System GE Multilin 7 2 TARGETS 7 COMMANDS AND TARGETS 7 ...
Page 748: ...D 10 G60 Generator Protection System GE Multilin D 1 IEC 60870 5 104 APPENDIX D D ...
Page 760: ...E 12 G60 Generator Protection System GE Multilin E 2 DNP POINT LISTS APPENDIX E E ...