GE Multilin
G60 Generator Protection System
2-25
2 PRODUCT DESCRIPTION
2.2 SPECIFICATIONS
2
2.2.8 FIELD AND STATOR GROUND MODULES
GPM-F MODULE CONTACT INPUTS
Internal wetting:
24 V DC
Input comparator threshold: 6 V DC
External contact:
dry
Current when energized: < 10 mA
Debounce time:
10 ms
GPM-F MODULE CRITICAL FAILURE RELAY
Make and carry:
30 A for 0.2 s as per ANSI C37.90
Continuous carry:
8 A
Break (DC inductive, L/R = 40 ms): 1 A at 24 V, 0.5 A at 48 V,
0.3 A at 125 V, 0.2 A at 250 V
Operate time:
< 8 ms
Contact material:
silver alloy
GPM-F MODULE POWER SUPPLY
GPM-F-L:
100 to 240V AC at 50/60Hz and 10 VA
125 to 250V DC at 10W
GPM-F-HM:
100 to 240V AC at 50/60Hz and 10 VA
125 to 250V DC at 10W
GPM-S-G MODULE CONTACT INPUTS
Internal wetting:
24 V DC
Input comparator threshold: 6 V DC
External contact:
dry
Current when energized: < 10 mA
Debounce time:
10 ms
GPM-S-G MODULE POWER SUPPLY
Power supply:
100 to 240 V AC at 50/60 Hz and 110VA
125 to 250 V DC at 110W
Output ratings:
26 V rectangular at 20 Hz, load capabil-
ity 80 VA
GPM-S-B MODULE
Power rating:
80VA
Input ratings:
maximum 30 V rectangular at 20 Hz
GPM-F-R MODULE
Current limiting resistor: 12.5
Ω
× 4
Voltage divider resistor: 5
Ω
× 3
STATOR GROUND PROTECTION CT
Part number:
204-SD-43737
Turns ratio:
400:5A
Rating factor (RF):
3.0
Frequency:
20 Hz
Voltage insulation:
600 V
Basic impulse level (BIL): 10 kV
Summary of Contents for Multilin g60
Page 10: ...x G60 Generator Protection System GE Multilin TABLE OF CONTENTS INDEX ...
Page 32: ...1 22 G60 Generator Protection System GE Multilin 1 5 USING THE RELAY 1 GETTING STARTED 1 ...
Page 160: ...4 30 G60 Generator Protection System GE Multilin 4 3 FACEPLATE INTERFACE 4 HUMAN INTERFACES 4 ...
Page 486: ...5 326 G60 Generator Protection System GE Multilin 5 10 TESTING 5 SETTINGS 5 ...
Page 518: ...6 32 G60 Generator Protection System GE Multilin 6 5 PRODUCT INFORMATION 6 ACTUAL VALUES 6 ...
Page 532: ...7 14 G60 Generator Protection System GE Multilin 7 2 TARGETS 7 COMMANDS AND TARGETS 7 ...
Page 748: ...D 10 G60 Generator Protection System GE Multilin D 1 IEC 60870 5 104 APPENDIX D D ...
Page 760: ...E 12 G60 Generator Protection System GE Multilin E 2 DNP POINT LISTS APPENDIX E E ...