B-38
G60 Generator Protection System
GE Multilin
B.4 MEMORY MAPPING
APPENDIX B
B
647D
...Repeated for Overfrequency 2
648A
...Repeated for Overfrequency 3
6497
...Repeated for Overfrequency 4
Power Swing Detect (Read/Write Grouped Setting)
65C0
Power Swing Detect Function
0 to 1
---
1
F102
0 (Disabled)
65C1
Power Swing Detect Source
0 to 5
---
1
F167
0 (SRC 1)
65C2
Power Swing Detect Mode
0 to 1
---
1
F513
0 (Two Step)
65C3
Power Swing Detect Supervision
0.05 to 30
pu
0.001
F001
600
65C4
Power Swing Detect Forward Reach
0.1 to 500
ohms
0.01
F001
5000
65C5
Power Swing Detect Forward RCA
40 to 90
degrees
1
F001
75
65C6
Power Swing Detect Reverse Reach
0.1 to 500
ohms
0.01
F001
5000
65C7
Power Swing Detect Reverse RCA
40 to 90
degrees
1
F001
75
65C8
Power Swing Detect Outer Limit Angle
40 to 140
degrees
1
F001
120
65C9
Power Swing Detect Middle Limit Angle
40 to 140
degrees
1
F001
90
65CA
Power Swing Detect Inner Limit Angle
40 to 140
degrees
1
F001
60
65CB
Power Swing Detect Delay 1 Pickup
0 to 65.535
s
0.001
F001
30
65CC
Power Swing Detect Delay 1 Reset
0 to 65.535
s
0.001
F001
50
65CD
Power Swing Detect Delay 2 Pickup
0 to 65.535
s
0.001
F001
17
65CE
Power Swing Detect Delay 3 Pickup
0 to 65.535
s
0.001
F001
9
65CF
Power Swing Detect Delay 4 Pickup
0 to 65.535
s
0.001
F001
17
65D0
Power Swing Detect Seal In Delay
0 to 65.535
s
0.001
F001
400
65D1
Power Swing Detect Trip Mode
0 to 1
---
1
F514
0 (Delayed)
65D2
Power Swing Detect Block
0 to 4294967295
---
1
F300
0
65D4
Power Swing Detect Target
0 to 2
---
1
F109
0 (Self-reset)
65D5
Power Swing Detect Event
0 to 1
---
1
F102
0 (Disabled)
65D6
Power Swing Detect Shape
0 to 1
---
1
F085
0 (Mho Shape)
65D7
Power Swing Detect Quad Forward Middle
0.1 to 500
ohms
0.01
F001
6000
65D8
Power Swing Detect Quad Forward Outer
0.1 to 500
ohms
0.01
F001
7000
65D9
Power Swing Detect Quad Reverse Middle
0.1 to 500
ohms
0.01
F001
6000
65DA
Power Swing Detect Quad Reverse Outer
0.1 to 500
ohms
0.01
F001
7000
65DB
Power Swing Detect Outer Right Blinder
0.1 to 500
ohms
0.01
F001
10000
65DC
Power Swing Detect Outer Left Blinder
0.1 to 500
ohms
0.01
F001
10000
65DD
Power Swing Detect Middle Right Blinder
0.1 to 500
ohms
0.01
F001
10000
65DE
Power Swing Detect Middle Left Blinder
0.1 to 500
ohms
0.01
F001
10000
65DF
Power Swing Detect Inner Right Blinder
0.1 to 500
ohms
0.01
F001
10000
65E0
Power Swing Detect Inner Left Blinder
0.1 to 500
ohms
0.01
F001
10000
Field Ground Actual Values (Read Only)
6640
Field Ground Resistance
0 to 20000
KOhm
0.001
F003
20000000
6642
Field Ground Current
0 to 655.35
mA
0.01
F001
0
6643
Field Ground Injected Voltage
-32.767 to 32.767
V
0.001
F002
0
6644
Field Ground Fault Location
-30000 to 30000
%
1
F002
-10
6645
Field Ground Field Voltage
-3276.8 to 3276.7
V
0.1
F002
0
6646
Field Current
-9999.999 to 9999.999
---
0.001
F004
0
6648
Field Current Units
---
---
---
F206
"A"
Accidental Energization (Read/Write Grouped Setting)
6650
Accidental Energization Function
0 to 1
---
1
F102
0 (Disabled)
6651
Accidental Energization Source
0 to 5
---
1
F167
0 (SRC 1)
6652
Accidental Energization Arming Mode
0 to 1
---
1
F193
0 (UV AND
OFFLINE)
6653
Accidental Energization OC Pickup
0 to 3
---
0.001
F003
300
6655
Accidental Energization UV Pickup
0 to 3
---
0.001
F003
500
6657
Accidental Energization Offline
0 to 4294967295
---
1
F300
0
6659
Accidental Energization Block
0 to 4294967295
---
1
F300
0
665B
Accidental Energization Target
0 to 2
---
1
F109
0 (Self-reset)
Table B–10: MODBUS MEMORY MAP (Sheet 30 of 68)
ADDR
REGISTER NAME
RANGE
UNITS
STEP
FORMAT
DEFAULT
Summary of Contents for Multilin g60
Page 10: ...x G60 Generator Protection System GE Multilin TABLE OF CONTENTS INDEX ...
Page 32: ...1 22 G60 Generator Protection System GE Multilin 1 5 USING THE RELAY 1 GETTING STARTED 1 ...
Page 160: ...4 30 G60 Generator Protection System GE Multilin 4 3 FACEPLATE INTERFACE 4 HUMAN INTERFACES 4 ...
Page 486: ...5 326 G60 Generator Protection System GE Multilin 5 10 TESTING 5 SETTINGS 5 ...
Page 518: ...6 32 G60 Generator Protection System GE Multilin 6 5 PRODUCT INFORMATION 6 ACTUAL VALUES 6 ...
Page 532: ...7 14 G60 Generator Protection System GE Multilin 7 2 TARGETS 7 COMMANDS AND TARGETS 7 ...
Page 748: ...D 10 G60 Generator Protection System GE Multilin D 1 IEC 60870 5 104 APPENDIX D D ...
Page 760: ...E 12 G60 Generator Protection System GE Multilin E 2 DNP POINT LISTS APPENDIX E E ...