GE Multilin
G60 Generator Protection System
5-27
5 SETTINGS
5.2 PRODUCT SETUP
5
5.2.4 COMMUNICATIONS
a) MAIN MENU
PATH: SETTINGS
PRODUCT SETUP
COMMUNICATIONS
b) SERIAL PORTS
The G60 is equipped with up to two independent serial communication ports. The faceplate RS232 port is intended for local
use and is fixed at 19200 baud and no parity. The rear COM2 port be used for either RS485 or RRTD communications.
PATH: SETTINGS
PRODUCT SETUP
COMMUNICATIONS
SERIAL PORTS
It is important that the baud rate and parity settings agree with the settings used on the computer or other equipment that is
connected to these ports.
COMMUNICATIONS
SERIAL PORTS
See below.
MESSAGE
NETWORK
MESSAGE
ROUTING
MESSAGE
MODBUS PROTOCOL
MESSAGE
DNP PROTOCOL
MESSAGE
DNP / IEC104
POINT LISTS
MESSAGE
IEC 61850 PROTOCOL
MESSAGE
WEB SERVER
HTTP PROTOCOL
MESSAGE
TFTP PROTOCOL
MESSAGE
IEC 60870-5-104
PROTOCOL
MESSAGE
EGD PROTOCOL
SERIAL PORTS
COM2 USAGE:
RS485
Range: RS485, RRTD only, GPM-F only,
RRTD & GPM-F
MESSAGE
RRTD SLAVE ADDRESS:
254
Range: 1 to 254 in steps of 1. Shown only if the COM2
USAGE is “RRTD only” or “RRTD & GPM-F”.
MESSAGE
RS485 COM2 BAUD
RATE: 19200
Range: 300, 1200, 2400, 4800, 9600, 14400, 19200,
28800, 33600, 38400, 57600, 115200. Shown
only if the COM2 USAGE is setting is “RS485”.
MESSAGE
RRTD BAUD RATE:
19200
Range: 1200, 2400, 4800, 9600, 19200. Shown only if
the COM2 USAGE is setting is “RRTD”.
MESSAGE
RS485 COM2 PARITY:
None
Range: None, Odd, Even.
MESSAGE
RS485 COM2 RESPONSE
MIN TIME:
0 ms
Range: 0 to 1000 ms in steps of 10
Summary of Contents for Multilin g60
Page 10: ...x G60 Generator Protection System GE Multilin TABLE OF CONTENTS INDEX ...
Page 32: ...1 22 G60 Generator Protection System GE Multilin 1 5 USING THE RELAY 1 GETTING STARTED 1 ...
Page 160: ...4 30 G60 Generator Protection System GE Multilin 4 3 FACEPLATE INTERFACE 4 HUMAN INTERFACES 4 ...
Page 486: ...5 326 G60 Generator Protection System GE Multilin 5 10 TESTING 5 SETTINGS 5 ...
Page 518: ...6 32 G60 Generator Protection System GE Multilin 6 5 PRODUCT INFORMATION 6 ACTUAL VALUES 6 ...
Page 532: ...7 14 G60 Generator Protection System GE Multilin 7 2 TARGETS 7 COMMANDS AND TARGETS 7 ...
Page 748: ...D 10 G60 Generator Protection System GE Multilin D 1 IEC 60870 5 104 APPENDIX D D ...
Page 760: ...E 12 G60 Generator Protection System GE Multilin E 2 DNP POINT LISTS APPENDIX E E ...