GE Multilin
G60 Generator Protection System
B-41
APPENDIX B
B.4 MEMORY MAPPING
B
7001
Phase Undervoltage 1 Signal Source
0 to 5
---
1
F167
0 (SRC 1)
7002
Phase Undervoltage 1 Pickup
0 to 3
pu
0.001
F001
1000
7003
Phase Undervoltage 1 Curve
0 to 1
---
1
F111
0 (Definite Time)
7004
Phase Undervoltage 1 Delay
0 to 600
s
0.01
F001
100
7005
Phase Undervoltage 1 Minimum Voltage
0 to 3
pu
0.001
F001
100
7006
Phase Undervoltage 1 Block
0 to 4294967295
---
1
F300
0
7008
Phase Undervoltage 1 Target
0 to 2
---
1
F109
0 (Self-reset)
7009
Phase Undervoltage 1 Events
0 to 1
---
1
F102
0 (Disabled)
700A
Phase Undervoltage 1 Measurement Mode
0 to 1
---
1
F186
0 (Phase to
Ground)
700B
Reserved (6 items)
0 to 1
---
1
F001
0
7013
...Repeated for Phase Undervoltage 2
7022
...Repeated for Phase Undervoltage 3
Phase Overvoltage (Read/Write Grouped Setting)
7040
Phase Overvoltage 1 Function
0 to 1
---
1
F102
0 (Disabled)
7041
Phase Overvoltage 1 Source
0 to 5
---
1
F167
0 (SRC 1)
7042
Phase Overvoltage 1 Pickup
0 to 3
pu
0.001
F001
1000
7043
Phase Overvoltage 1 Delay
0 to 600
s
0.01
F001
100
7044
Phase Overvoltage 1 Reset Delay
0 to 600
s
0.01
F001
100
7045
Phase Overvoltage 1 Block
0 to 4294967295
---
1
F300
0
7047
Phase Overvoltage 1 Target
0 to 2
---
1
F109
0 (Self-reset)
7048
Phase Overvoltage 1 Events
0 to 1
---
1
F102
0 (Disabled)
7049
Reserved (8 items)
0 to 1
---
1
F001
0
Distance (Read/Write Grouped Setting)
7060
Distance Signal Source
0 to 5
---
1
F167
0 (SRC 1)
7061
Memory Duration
5 to 25
cycles
1
F001
10
7062
Force Self-Polarization
0 to 4294967295
---
1
F300
0
7064
Force Memory Polarization
0 to 4294967295
---
1
F300
0
Phase Distance (Read/Write Grouped Setting) (3 modules)
7070
Phase Distance Zone 1 Function
0 to 1
---
1
F102
0 (Disabled)
7071
Phase Distance Zone 1 Current Supervision
0.05 to 30
pu
0.001
F001
200
7072
Phase Distance Zone 1 Reach
0.02 to 500
ohms
0.01
F001
200
7073
Phase Distance Zone 1 Direction
0 to 2
---
1
F154
0 (Forward)
7074
Phase Distance Zone 1 Comparator Limit
30 to 90
degrees
1
F001
90
7075
Phase Distance Zone 1 Delay
0 to 65.535
s
0.001
F001
0
7076
Phase Distance Zone 1 Block
0 to 4294967295
---
1
F300
0
7078
Phase Distance Zone 1 Target
0 to 2
---
1
F109
0 (Self-reset)
7079
Phase Distance Zone 1 Events
0 to 1
---
1
F102
0 (Disabled)
707A
Phase Distance Zone 1 Shape
0 to 1
---
1
F120
0 (Mho)
Fixed in G60
707B
Phase Distance Zone 1 RCA
30 to 90
degrees
1
F001
85
707C
Phase Distance Zone 1 DIR RCA
30 to 90
degrees
1
F001
85
707D
Phase Distance Zone 1 DIR Comp Limit
30 to 90
degrees
1
F001
90
7082
Phase Distance Zone 1 Volt Limit
0 to 5
pu
0.001
F001
0
7083
Phase Distance Zone 1 Transformer Voltage Connection
0 to 12
---
1
F153
0 (None)
7084
Phase Distance Zone 1 Transformer Current Connection
0 to 12
---
1
F153
0 (None)
7085
Phase Distance Zone 1 Rev Reach
0.02 to 500
ohms
0.01
F001
200
7086
Phase Distance Zone 1 Rev Reach RCA
30 to 90
degrees
1
F001
85
7087
Reserved (10 items)
---
---
---
F001
0
7091
...Repeated for Phase Distance Zone 2
70B2
...Repeated for Phase Distance Zone 3
Phase Directional Overcurrent (Read/Write Grouped Setting)
7200
Phase Directional Overcurrent 1 Function
0 to 1
---
1
F102
0 (Disabled)
7201
Phase Directional Overcurrent 1 Source
0 to 5
---
1
F167
0 (SRC 1)
Table B–10: MODBUS MEMORY MAP (Sheet 33 of 68)
ADDR
REGISTER NAME
RANGE
UNITS
STEP
FORMAT
DEFAULT
Summary of Contents for Multilin g60
Page 10: ...x G60 Generator Protection System GE Multilin TABLE OF CONTENTS INDEX ...
Page 32: ...1 22 G60 Generator Protection System GE Multilin 1 5 USING THE RELAY 1 GETTING STARTED 1 ...
Page 160: ...4 30 G60 Generator Protection System GE Multilin 4 3 FACEPLATE INTERFACE 4 HUMAN INTERFACES 4 ...
Page 486: ...5 326 G60 Generator Protection System GE Multilin 5 10 TESTING 5 SETTINGS 5 ...
Page 518: ...6 32 G60 Generator Protection System GE Multilin 6 5 PRODUCT INFORMATION 6 ACTUAL VALUES 6 ...
Page 532: ...7 14 G60 Generator Protection System GE Multilin 7 2 TARGETS 7 COMMANDS AND TARGETS 7 ...
Page 748: ...D 10 G60 Generator Protection System GE Multilin D 1 IEC 60870 5 104 APPENDIX D D ...
Page 760: ...E 12 G60 Generator Protection System GE Multilin E 2 DNP POINT LISTS APPENDIX E E ...