5-204
G60 Generator Protection System
GE Multilin
5.6 GROUPED ELEMENTS
5 SETTINGS
5
The positive-sequence restraint must be considered when testing for pick-up accuracy and response time (multiple of
pickup). The positive-sequence restraint is removed for low currents. If the positive-sequence current is less than 0.8 pu,
then the restraint is removed by changing the constant
K
to zero. This results in better response to high-resistance faults
when the unbalance is very small and there is no danger of excessive CT errors, since the current is low.
The
operating quantity
depends on the way the test currents are injected into the G60. For single phase injection:
•
I
op
=
⅓
×
(1 –
K
) ×
I
injected
for I_2 mode.
•
I
op
= (1 –
K
) ×
I
injected
for I_0 mode if I_1 > 0.8 pu.
The
directional unit
uses the negative-sequence current (I_2) and negative-sequence voltage (V_2).
The following tables define the negative-sequence directional overcurrent element.
Table 5–29: NEGATIVE-SEQUENCE DIRECTIONAL OVERCURRENT UNIT
Table 5–30: NEGATIVE-SEQUENCE DIRECTIONAL UNIT
The negative-sequence voltage must be greater than the
VOLTAGE CUTOFF LEVEL
setting specified in the
PRODUCT SETUP
DISPLAY PROPERTIES
menu to be validated for use as a polarizing signal. If the polarizing signal is not validated neither
forward nor reverse indication is given. The following figure explains the usage of the voltage polarized directional unit of
the element.
The figure below shows the phase angle comparator characteristics for a phase A to ground fault, with settings of:
ECA
= 75° (element characteristic angle = centerline of operating characteristic)
FWD LA = 80° (forward limit angle = ± the angular limit with the ECA for operation)
REV LA
= 80° (reverse limit angle = ± the angular limit with the ECA for operation)
MODE
OPERATING CURRENT
Negative-sequence
I
op
= |I_2| –
K
×
I_1|
Zero-sequence
I
op
= 3 × (|I_0| –
K
× |I_1|) if |I_1| > 0.8 pu
I
op
= 3 × |I_0| if |I_1|
≤
0.8 pu
DIRECTION
COMPARED PHASORS
Forward
–V_2
+
Z_offset
×
I_2
I_2
×
1
∠
ECA
Reverse
–V_2
+
Z_offset
×
I_2
–(I_2
×
1
∠
ECA)
Forward
–V_2
+
Z_offset
×
I_2
I_2
×
1
∠
ECA
Reverse
–V_2
+
Z_offset
×
I_2
–(I_2
×
1
∠
ECA)
Summary of Contents for Multilin g60
Page 10: ...x G60 Generator Protection System GE Multilin TABLE OF CONTENTS INDEX ...
Page 32: ...1 22 G60 Generator Protection System GE Multilin 1 5 USING THE RELAY 1 GETTING STARTED 1 ...
Page 160: ...4 30 G60 Generator Protection System GE Multilin 4 3 FACEPLATE INTERFACE 4 HUMAN INTERFACES 4 ...
Page 486: ...5 326 G60 Generator Protection System GE Multilin 5 10 TESTING 5 SETTINGS 5 ...
Page 518: ...6 32 G60 Generator Protection System GE Multilin 6 5 PRODUCT INFORMATION 6 ACTUAL VALUES 6 ...
Page 532: ...7 14 G60 Generator Protection System GE Multilin 7 2 TARGETS 7 COMMANDS AND TARGETS 7 ...
Page 748: ...D 10 G60 Generator Protection System GE Multilin D 1 IEC 60870 5 104 APPENDIX D D ...
Page 760: ...E 12 G60 Generator Protection System GE Multilin E 2 DNP POINT LISTS APPENDIX E E ...