GE Multilin
G60 Generator Protection System
3-63
3 HARDWARE
3.4 FIELD AND STATOR GROUND MODULES
3
Figure 3–71: REAR VIEW OF GPM-S-G MODULE SHOWING TERMINAL BLOCKS
The following tables outline the pin assignments for the stator ground 20 Hz generator module. Two contact inputs are pro-
vided. Upon closure of any one of the contact inputs, 20 Hz injection stops.
There are two connectors on the stator ground protection band pass filter module, as shown in the following figure.
Table 3–14: GPM-S-G PIN ASSIGNMENTS FOR CONNECTOR A
PIN
LABEL
DEFINITION
1
A1
Contact input 1
2
A2
Contact input 2
3
A3
Alarm relay NC (normally closed)
4
A4
Not used
5
A5
Output 1
6
A6
Contact input common
7
A7
Alarm relay NO (normally open)
8
A8
Alarm relay common
9
A9
Not used
10
A10
Output 2
Table 3–15: GPM-S-G PIN ASSIGNMENTS FOR CONNECTOR B
PIN
LABEL
DEFINITION
1
B1
Not used
2
B2
Not used
3
B3
Not used
4
B4
Not used
5
B5
Not used
6
B6
Not used
7
B7
Not used
8
B8
Ground
9
B9
Power neutral / DC negative
10
B10
Power line / DC positive
$&'5
$
%
Summary of Contents for Multilin g60
Page 10: ...x G60 Generator Protection System GE Multilin TABLE OF CONTENTS INDEX ...
Page 32: ...1 22 G60 Generator Protection System GE Multilin 1 5 USING THE RELAY 1 GETTING STARTED 1 ...
Page 160: ...4 30 G60 Generator Protection System GE Multilin 4 3 FACEPLATE INTERFACE 4 HUMAN INTERFACES 4 ...
Page 486: ...5 326 G60 Generator Protection System GE Multilin 5 10 TESTING 5 SETTINGS 5 ...
Page 518: ...6 32 G60 Generator Protection System GE Multilin 6 5 PRODUCT INFORMATION 6 ACTUAL VALUES 6 ...
Page 532: ...7 14 G60 Generator Protection System GE Multilin 7 2 TARGETS 7 COMMANDS AND TARGETS 7 ...
Page 748: ...D 10 G60 Generator Protection System GE Multilin D 1 IEC 60870 5 104 APPENDIX D D ...
Page 760: ...E 12 G60 Generator Protection System GE Multilin E 2 DNP POINT LISTS APPENDIX E E ...