2-26
G60 Generator Protection System
GE Multilin
2.2 SPECIFICATIONS
2 PRODUCT DESCRIPTION
2
GPM-F-HM, GPM-F-L, GPM-F-R, GPM-S-B, AND GPM-S-G MODULE TYPE TESTS
TEST
REFERENCE STANDARD
TEST LEVEL
GPM-F TYPES
GPM-S TYPES
Dielectric voltage withstand
EN60255-5
2.3 kV AC / 4.6 kV DC
2.3 kV AC / 3.3 kV DC
Impulse voltage withstand
EN60255-5
5 kV
5 kV
Insulation
EN60255-5
500 V DC
500 V DC
Damped oscillatory
IEC61000-4-18IEC60255-22-1
2.5 kV CM, 1 kV DM
2.5 kV CM, 1 kV DM
Electrostatic discharge
EN61000-4-2/IEC60255-22-2
Level 4
Level 4
RF immunity
EN61000-4-3/IEC60255-22-3
20 V/m
20 V/m
Fast Transient Disturbance
EN61000-4-4/IEC60255-22-4
Class A and B
Class A and B
Surge Immunity
EN61000-4-5/IEC60255-22-5
Level 4
Level 4
Conducted RF Immunity
EN61000-4-6/IEC60255-22-6
Level 3
Level 3
Voltage interruption and ripple DC
IEC60255-11
15% ripple,
1 ms to 5 s interrupts
15% ripple,
1 ms to 5 s interrupts
Radiated and conducted emissions
CISPR11 / CISPR22 / IEC60255-25
Class A
Class A
Sinusoidal vibration
IEC60255-21-1
Class 2
Class 1
Shock and Bump
IEC60255-21-2
Class 2
Class 1
Seismic
IEC60255-21-3
Class 2
Class 1
Power magnetic immunity
IEC61000-4-8
Level 5
Level 5
Pulse magnetic immunity
IEC61000-4-9
Level 4
Level 4
Damped magnetic immunity
IEC61000-4-10
Level 4
Level 4
Voltage dip and interruption
IEC61000-4-11
0%, 40%, 70%, 80% dips;
250/300 cycle interrupts
0%, 40%, 70%, 80% dips;
250/300 cycle interrupts
Voltage ripple
IEC61000-4-17
15% ripple
15% ripple
Ingress protection
IEC60529
IP10
IP10
Environmental (cold)
IEC60068-2-1
–40°C, 16 hrs
–40°C, 16 hrs
Environmental (dry heat)
IEC60068-2-2
85°C, 16hrs
85°C, 16hrs
Relative humidity cyclic
IEC60068-2-30
6 day, variant 1
6 day, variant 1
SWC oscillatory
IEEE/ANSI C37.90.1
2.5 kV,1 MHz
2.5 kV,1 MHz
SWC transients
IEEE/ANSI C37.90.1
4 kV 2.5 kHz
4 kV 2.5 kHz
RF immunity
IEEE/ANSIC37.90.2
20 V/m
20 V/m
ESD
IEEE/ANSIC37.90.3
15 kV air / 8 kV contact
15 kV air / 8 kV contact
Safety
UL508
e83849 NKCR2
e83849 NKCR2
UL C22.2-14
e83849 NKCR8
e83849 NKCR8
Summary of Contents for Multilin g60
Page 10: ...x G60 Generator Protection System GE Multilin TABLE OF CONTENTS INDEX ...
Page 32: ...1 22 G60 Generator Protection System GE Multilin 1 5 USING THE RELAY 1 GETTING STARTED 1 ...
Page 160: ...4 30 G60 Generator Protection System GE Multilin 4 3 FACEPLATE INTERFACE 4 HUMAN INTERFACES 4 ...
Page 486: ...5 326 G60 Generator Protection System GE Multilin 5 10 TESTING 5 SETTINGS 5 ...
Page 518: ...6 32 G60 Generator Protection System GE Multilin 6 5 PRODUCT INFORMATION 6 ACTUAL VALUES 6 ...
Page 532: ...7 14 G60 Generator Protection System GE Multilin 7 2 TARGETS 7 COMMANDS AND TARGETS 7 ...
Page 748: ...D 10 G60 Generator Protection System GE Multilin D 1 IEC 60870 5 104 APPENDIX D D ...
Page 760: ...E 12 G60 Generator Protection System GE Multilin E 2 DNP POINT LISTS APPENDIX E E ...