GE Multilin
G60 Generator Protection System
B-47
APPENDIX B
B.4 MEMORY MAPPING
B
Auxiliary Undervoltage (Read/Write Grouped Setting) (3 modules)
7F60
Auxiliary Undervoltage 1 Function
0 to 1
---
1
F102
0 (Disabled)
7F61
Auxiliary Undervoltage 1 Signal Source
0 to 5
---
1
F167
0 (SRC 1)
7F62
Auxiliary Undervoltage 1 Pickup
0 to 3
pu
0.001
F001
700
7F63
Auxiliary Undervoltage 1 Delay
0 to 600
s
0.01
F001
100
7F64
Auxiliary Undervoltage 1 Curve
0 to 1
---
1
F111
0 (Definite Time)
7F65
Auxiliary Undervoltage 1 Minimum Voltage
0 to 3
pu
0.001
F001
100
7F66
Auxiliary Undervoltage 1 Block
0 to 4294967295
---
1
F300
0
7F68
Auxiliary Undervoltage 1 Target
0 to 2
---
1
F109
0 (Self-reset)
7F69
Auxiliary Undervoltage 1 Events
0 to 1
---
1
F102
0 (Disabled)
7F6A
Reserved (7 items)
0 to 65535
---
1
F001
0
7F71
...Repeated for Auxiliary Undervoltage 2
7F82
...Repeated for Auxiliary Undervoltage 3
Auxiliary Overvoltage (Read/Write Grouped Setting) (3 modules)
7FA0
Auxiliary Overvoltage 1 Function
0 to 1
---
1
F102
0 (Disabled)
7FA1
Auxiliary Overvoltage 1 Signal Source
0 to 5
---
1
F167
0 (SRC 1)
7FA2
Auxiliary Overvoltage 1 Pickup
0 to 3
pu
0.001
F001
300
7FA3
Auxiliary Overvoltage 1 Pickup Delay
0 to 600
s
0.01
F001
100
7FA4
Auxiliary Overvoltage 1 Reset Delay
0 to 600
s
0.01
F001
100
7FA5
Auxiliary Overvoltage 1 Block
0 to 4294967295
---
1
F300
0
7FA7
Auxiliary Overvoltage 1 Target
0 to 2
---
1
F109
0 (Self-reset)
7FA8
Auxiliary Overvoltage 1 Events
0 to 1
---
1
F102
0 (Disabled)
7FA9
Reserved (8 items)
0 to 65535
---
1
F001
0
7FB1
...Repeated for Auxiliary Overvoltage 2
7FC2
...Repeated for Auxiliary Overvoltage 3
Frequency (Read Only)
8000
Tracking Frequency
2 to 90
Hz
0.01
F001
0
Temp Monitor Actual Values (Read Only Non-Volatile)
81C0
Reserved Register T1
-55 to 125
C
1
F002
-55
81C1
Reserved Register T2
-55 to 125
C
1
F002
125
81C2
Reserved Register T3
-2147483647 to
2147483647
---
1
F004
0
81C4
Reserved Register T4
0 to 4294967295
---
1
F003
0
81C6
Reserved Register T5
0 to 4294967295
---
1
F003
0
81C8
Reserved Register T6
0 to 4294967295
---
1
F003
0
81CA
Reserved Register T7
0 to 4294967295
---
1
F003
0
81CC
Reserved Register T8
0 to 4294967295
---
1
F003
0
EGD Fast Production Status (Read Only Non-Volatile and Read Only)
83E0
EGD Fast Producer Exchange 1 Signature
0 to 65535
---
1
F001
0
83E1
EGD Fast Producer Exchange 1 Configuration Time
0 to 4294967295
---
---
F003
0
83E3
EGD Fast Producer Exchange 1 Size
0 to 65535
---
1
F001
0
EGD Slow Production Status (Read Only Non-Volatile and Read Only) (2 modules)
83F0
EGD Slow Producer Exchange 1 Signature
0 to 65535
---
1
F001
0
83F1
EGD Slow Producer Exchange 1 Configuration Time
0 to 4294967295
---
---
F003
0
83F3
EGD Slow Producer Exchange 1 Size
0 to 65535
---
1
F001
0
83F4
...Repeated for EGD Slow Producer Exchange 2
EGD Fast Production (Read/Write Setting)
8400
EGD Fast Producer Exchange 1 Function
0 to 1
---
1
F102
0 (Disabled)
8401
EGD Fast Producer Exchange 1 Destination
0 to 4294967295
---
1
F003
0
8403
EGD Fast Producer Exchange 1 Data Rate
50 to 1000
ms
50
F001
1000
8404
EGD Fast Producer Exchange 1 Data Item 1 (20 items)
0 to 65535
---
1
F001
0
8418
Reserved (80 items)
---
---
---
F001
0
EGD Slow Production (Read/Write Setting) (2 modules)
8468
EGD Slow Producer Exchange 1 Function
0 to 1
---
1
F102
0 (Disabled)
Table B–10: MODBUS MEMORY MAP (Sheet 39 of 68)
ADDR
REGISTER NAME
RANGE
UNITS
STEP
FORMAT
DEFAULT
Summary of Contents for Multilin g60
Page 10: ...x G60 Generator Protection System GE Multilin TABLE OF CONTENTS INDEX ...
Page 32: ...1 22 G60 Generator Protection System GE Multilin 1 5 USING THE RELAY 1 GETTING STARTED 1 ...
Page 160: ...4 30 G60 Generator Protection System GE Multilin 4 3 FACEPLATE INTERFACE 4 HUMAN INTERFACES 4 ...
Page 486: ...5 326 G60 Generator Protection System GE Multilin 5 10 TESTING 5 SETTINGS 5 ...
Page 518: ...6 32 G60 Generator Protection System GE Multilin 6 5 PRODUCT INFORMATION 6 ACTUAL VALUES 6 ...
Page 532: ...7 14 G60 Generator Protection System GE Multilin 7 2 TARGETS 7 COMMANDS AND TARGETS 7 ...
Page 748: ...D 10 G60 Generator Protection System GE Multilin D 1 IEC 60870 5 104 APPENDIX D D ...
Page 760: ...E 12 G60 Generator Protection System GE Multilin E 2 DNP POINT LISTS APPENDIX E E ...