7926
PMU 1 Ic Calibration Magnitude
95 to 105
%
0.1
F002
1000
7927
PMU 1 Ig Calibration Angle
-5 to 5
°
0.05
F002
0
7928
PMU 1 Ig Calibration Magnitude
95 to 105
%
0.1
F002
1000
7929
PMU 1 Sequence Voltage Shift Angle
-180 to 180
°
30
F002
0
792A
PMU 1 Sequence Current Shift Angle
-180 to 180
°
30
F002
0
Phasor Measurement Unit Triggering (Read/Write Setting)
7970
PMU 1 User Trigger
0 to 4294967295
---
1
F300
0
Phasor Measurement Unit Current Trigger (Read/Write Setting)
7980
PMU 1 Current Trigger Function
0 to 1
---
1
F102
0 (Disabled)
7981
PMU 1 Current Trigger Pickup
0.1 to 30
pu
0.001
F001
1800
7982
PMU 1 Current Trigger Pickup Time
0 to 600
s
0.01
F001
10
7983
PMU 1 Current Trigger Dropout Time
0 to 600
s
0.01
F001
100
7984
PMU 1 Current Trigger Block (3 items)
0 to 4294967295
---
1
F300
0
798A
PMU 1 Current Trigger Target
0 to 2
---
1
F109
0 (Self-reset)
798B
PMU 1 Current Trigger Events
0 to 1
---
1
F102
0 (Disabled)
Phasor Measurement Unit df/dt Trigger (Read/Write Setting)
79B0
PMU 1 df/dt Trigger Function
0 to 1
---
1
F102
0 (Disabled)
79B1
PMU 1 df/dt Trigger Raise
0.1 to 15
Hz/s
0.01
F001
25
79B2
PMU 1 df/dt Trigger Fall
0.1 to 15
Hz/s
0.01
F001
25
79B3
PMU 1 df/dt Trigger Pickup Time
0 to 600
s
0.01
F001
10
79B4
PMU 1 df/dt Trigger Dropout Time
0 to 600
s
0.01
F001
100
79B5
PMU 1 df/dt Trigger Block (3 items)
0 to 4294967295
---
1
F300
0
79BB
PMU 1 df/dt Trigger Target
0 to 2
---
1
F109
0 (Self-reset)
79BC
PMU 1 df/dt Trigger Events
0 to 1
---
1
F102
0 (Disabled)
Field Current Protection Settings (Read/Write Grouped Setting)
7A60
Field Current Function
0 to 1
---
1
F102
0 (Disabled)
7A61
Field Current Origin
0 to 48
---
1
F151
0 (NONE)
7A62
Field Current OC Pickup
0.05 to 1
pu
0.01
F001
80
7A63
Field Current OC Delay
0 to 600
s
0.01
F001
100
7A64
Field Current UC Pickup
0.05 to 1
pu
0.01
F001
20
7A65
Field Current UC Delay
0 to 600
s
0.01
F001
100
7A66
Field Current Block
0 to 4294967295
---
1
F300
0
7A68
Field Current Target
0 to 2
---
1
F109
0 (Self-reset)
7A69
Field Current Events
0 to 1
---
1
F102
0 (Disabled)
Field Ground Protection Settings (Read/Write Grouped Setting)
7A6A
Field Ground Function
0 to 1
---
1
F102
0 (Disabled)
7A6B
Field Ground Injection Frequency
0.1 to 3
Hz
0.01
F001
100
7A6C
Field Ground Inj Connection Type
0 to 1
---
1
F613
0 (Single Point)
7A6D
Field Ground STG1 Pickup
1 to 500
kohms
1
F001
20
7A6E
Field Ground STG1 Delay
0.1 to 600
s
0.1
F001
100
7A6F
Field Ground STG2 Pickup
1 to 500
kohms
1
F001
5
7A70
Field Ground STG2 Delay
0.1 to 600
s
0.1
F001
30
7A71
Field Ground UC Pickup
0.05 to 100
mA
0.01
F001
100
7A72
Field Ground UC Delay
0.1 to 600
s
0.01
F001
100
7A73
Field Ground Block
0 to 4294967295
---
1
F300
0
7A75
Field Ground Target
0 to 2
---
1
F109
0 (Self-reset)
7A76
Field Ground Events
0 to 1
---
1
F102
0 (Disabled)
Underfrequency (Read/Write Setting) (6 modules)
7A80
Underfrequency 1 Function
0 to 1
---
1
F102
0 (Disabled)
7A81
Underfrequency 1 Block
0 to 4294967295
---
1
F300
0
7A83
Underfrequency 1 Min Current
0.1 to 1.25
pu
0.01
F001
10
7A84
Underfrequency 1 Pickup
20 to 65
Hz
0.01
F001
5950
7A85
Underfrequency 1 Pickup Delay
0 to 65.535
s
0.001
F001
2000
7A86
Underfrequency 1 Reset Delay
0 to 65.535
s
0.001
F001
2000
Table B–10: MODBUS MEMORY MAP (Sheet 37 of 68)
ADDR
REGISTER NAME
RANGE
UNITS
STEP
FORMAT
DEFAULT
Summary of Contents for Multilin g60
Page 10: ...x G60 Generator Protection System GE Multilin TABLE OF CONTENTS INDEX ...
Page 32: ...1 22 G60 Generator Protection System GE Multilin 1 5 USING THE RELAY 1 GETTING STARTED 1 ...
Page 160: ...4 30 G60 Generator Protection System GE Multilin 4 3 FACEPLATE INTERFACE 4 HUMAN INTERFACES 4 ...
Page 486: ...5 326 G60 Generator Protection System GE Multilin 5 10 TESTING 5 SETTINGS 5 ...
Page 518: ...6 32 G60 Generator Protection System GE Multilin 6 5 PRODUCT INFORMATION 6 ACTUAL VALUES 6 ...
Page 532: ...7 14 G60 Generator Protection System GE Multilin 7 2 TARGETS 7 COMMANDS AND TARGETS 7 ...
Page 748: ...D 10 G60 Generator Protection System GE Multilin D 1 IEC 60870 5 104 APPENDIX D D ...
Page 760: ...E 12 G60 Generator Protection System GE Multilin E 2 DNP POINT LISTS APPENDIX E E ...