GE Multilin
G60 Generator Protection System
5-275
5 SETTINGS
5.7 CONTROL ELEMENTS
5
b) SPECIAL APPLICATION OF THE SYNCHROCHECK ELEMENT
The synchrocheck element is intended for applications where the potential sources are located on either side of the breaker
to be closed. It can also be used in cases where a power transformer is located between the two potential sources by com-
pensating for the power transformer phase shift with the auxiliary VT connection to the G60 and the auxiliary VT connection
setting, as shown in the following example.
Figure 5–148: SYNCHROCHECK APPLIED ACROSS A TRANSFORMER
In this example, the phase voltage VT input is programmed as “Delta” with a secondary setting of 120 volts and a ratio of
13800 V/ 120 V = 115. The auxiliary VT connection is selected to be VAB since this vector is in phase with VA on the trans-
former primary. The secondary setting is 69 volts and the auxiliary VT ratio is calculated as 13800 V / 69 V = 200. Note that
the metered values for the auxiliary VT will now reflect the AB voltage of the secondary side of the transformer.
Phase VT input
A
B
C
a
b
c
System nominal
Vpp = 13.8 kV
System nominal
Vpp = 230 kV
138000 : 69
14400 : 120
~5a
52
~5c ~6a ~6c ~7a ~7c
~8a
~8c
Auxiliary VT input
UR-series device
843808A2.CDR
Summary of Contents for Multilin g60
Page 10: ...x G60 Generator Protection System GE Multilin TABLE OF CONTENTS INDEX ...
Page 32: ...1 22 G60 Generator Protection System GE Multilin 1 5 USING THE RELAY 1 GETTING STARTED 1 ...
Page 160: ...4 30 G60 Generator Protection System GE Multilin 4 3 FACEPLATE INTERFACE 4 HUMAN INTERFACES 4 ...
Page 486: ...5 326 G60 Generator Protection System GE Multilin 5 10 TESTING 5 SETTINGS 5 ...
Page 518: ...6 32 G60 Generator Protection System GE Multilin 6 5 PRODUCT INFORMATION 6 ACTUAL VALUES 6 ...
Page 532: ...7 14 G60 Generator Protection System GE Multilin 7 2 TARGETS 7 COMMANDS AND TARGETS 7 ...
Page 748: ...D 10 G60 Generator Protection System GE Multilin D 1 IEC 60870 5 104 APPENDIX D D ...
Page 760: ...E 12 G60 Generator Protection System GE Multilin E 2 DNP POINT LISTS APPENDIX E E ...