5-290
G60 Generator Protection System
GE Multilin
5.7 CONTROL ELEMENTS
5 SETTINGS
5
To ensure element accuracy for high overcurrent conditions, the maximum value of I/(k x I
B
) is limited to 8, even when real-
istically it is exceeding this value.
The reset time of the thermal overload protection element is also time delayed using following formula:
(EQ 5.50)
In the above equation,
•
τ
rst
= thermal protection trip time constant.
•
T
min
is a minimum reset time setting
Figure 5–156: IEC 255-8 SAMPLE OPERATE AND RESET CURVES
The thermal overload protection element estimates accumulated thermal energy
E
using the following equations calculated
each power cycle. When current is greater than the pickup level,
I
n
>
k
×
I
B
, element starts increasing the thermal energy:
(EQ 5.51)
When current is less than the dropout level,
I
n
> 0.97 ×
k
×
I
B
, the element starts decreasing the thermal energy:
t
rst
τ
rst
kI
B
(
)
2
I
2
kI
B
(
)
2
–
-----------------------------
ln
×
T
min
+
=
0.1
1
10
100
I / Ipkp
t (min)
0.01
0.1
1
10
100
τ
= 30
rst
τ
= 30
op
T
= 10
min
827724A1.CDR
E
n
E
n
1
–
t
Δ
t
op In
( )
---------------
+
=
Summary of Contents for Multilin g60
Page 10: ...x G60 Generator Protection System GE Multilin TABLE OF CONTENTS INDEX ...
Page 32: ...1 22 G60 Generator Protection System GE Multilin 1 5 USING THE RELAY 1 GETTING STARTED 1 ...
Page 160: ...4 30 G60 Generator Protection System GE Multilin 4 3 FACEPLATE INTERFACE 4 HUMAN INTERFACES 4 ...
Page 486: ...5 326 G60 Generator Protection System GE Multilin 5 10 TESTING 5 SETTINGS 5 ...
Page 518: ...6 32 G60 Generator Protection System GE Multilin 6 5 PRODUCT INFORMATION 6 ACTUAL VALUES 6 ...
Page 532: ...7 14 G60 Generator Protection System GE Multilin 7 2 TARGETS 7 COMMANDS AND TARGETS 7 ...
Page 748: ...D 10 G60 Generator Protection System GE Multilin D 1 IEC 60870 5 104 APPENDIX D D ...
Page 760: ...E 12 G60 Generator Protection System GE Multilin E 2 DNP POINT LISTS APPENDIX E E ...