GE Multilin
G60 Generator Protection System
5-145
5 SETTINGS
5.5 FLEXLOGIC
5
FIXED OPERANDS
Off
Logic = 0. Does nothing and may be used as a delimiter in an equation list;
used as ‘Disable’ by other features.
On
Logic = 1. Can be used as a test setting.
INPUTS/OUTPUTS:
Contact inputs
Cont Ip 1
On
Cont Ip 2
On
↓
Cont Ip 1
Off
Cont Ip 2
Off
↓
Cont Ip 96
On
Cont Ip 96
Off
(will not appear unless ordered)
(will not appear unless ordered)
↓
(will not appear unless ordered)
(will not appear unless ordered)
↓
(will not appear unless ordered)
(will not appear unless ordered)
INPUTS/OUTPUTS:
Contact outputs,
current
(from detector on
form-A output only)
Cont Op 1 IOn
Cont Op 2 IOn
↓
(will not appear unless ordered)
(will not appear unless ordered)
↓
INPUTS/OUTPUTS:
Contact outputs,
voltage
(from detector on
form-A output only)
Cont Op 1 VOn
Cont Op 2 VOn
↓
(will not appear unless ordered)
(will not appear unless ordered)
↓
Cont Op 1 VOff
Cont Op 2 VOff
↓
(will not appear unless ordered)
(will not appear unless ordered)
↓
INPUTS/OUTPUTS
Direct inputs
DIRECT INPUT 1 On
↓
DIRECT INPUT 32 On
Flag is set, logic=1
↓
Flag is set, logic=1
INPUTS/OUTPUTS:
Remote double-
point status inputs
RemDPS Ip 1 BAD
RemDPS Ip 1 INTERM
RemDPS Ip 1 OFF
RemDPS Ip 1 ON
Asserted while the remote double-point status input is in the bad state
Asserted while the remote double-point status input is in the intermediate
state
Asserted while the remote double-point status input is off
Asserted while the remote double-point status input is on
REMDPS Ip 2...
Same set of operands as per REMDPS 1 above
INPUTS/OUTPUTS:
Remote inputs
REMOTE INPUT 1 On
REMOTE INPUT 2 On
REMOTE INPUT 3 On
↓
REMOTE INPUT 32 On
Flag is set, logic=1
Flag is set, logic=1
Flag is set, logic=1
↓
Flag is set, logic=1
INPUTS/OUTPUTS:
Virtual inputs
Virt Ip 1
On
Virt Ip 2
On
Virt Ip 3
On
↓
Virt Ip 64
On
Flag is set, logic=1
Flag is set, logic=1
Flag is set, logic=1
↓
Flag is set, logic=1
INPUTS/OUTPUTS:
Virtual outputs
Virt Op 1 On
Virt Op 2 On
Virt Op 3 On
↓
Virt Op 96 On
Flag is set, logic=1
Flag is set, logic=1
Flag is set, logic=1
↓
Flag is set, logic=1
LED INDICATORS:
Fixed front panel
LEDs
LED IN SERVICE
LED TROUBLE
LED TEST MODE
LED TRIP
LED ALARM
LED PICKUP
LED VOLTAGE
LED CURRENT
LED FREQUENCY
LED OTHER
LED PHASE A
LED PHASE B
LED PHASE C
LED NEUTRAL/GROUND
Asserted when the front panel IN SERVICE LED is on
Asserted when the front panel TROUBLE LED is on
Asserted when the front panel TEST MODE LED is on
Asserted when the front panel TRIP LED is on
Asserted when the front panel ALARM LED is on
Asserted when the front panel PICKUP LED is on
Asserted when the front panel VOLTAGE LED is on
Asserted when the front panel CURRENT LED is on
Asserted when the front panel FREQUENCY LED is on
Asserted when the front panel OTHER LED is on
Asserted when the front panel PHASE A LED is on
Asserted when the front panel PHASE B LED is on
Asserted when the front panel PHASE C LED is on
Asserted when the front panel NEUTRAL/GROUND LED is on
LED INDICATORS:
LED test
LED TEST IN PROGRESS
An LED test has been initiated and has not finished
LED INDICATORS:
User-programmable
LEDs
LED USER 1
Asserted when user-programmable LED 1 is on
LED USER 2 to 48
The operand above is available for user-programmable LEDs 2 through 48
Table 5–15: G60 FLEXLOGIC OPERANDS (Sheet 8 of 9)
OPERAND TYPE
OPERAND SYNTAX
OPERAND DESCRIPTION
Summary of Contents for Multilin g60
Page 10: ...x G60 Generator Protection System GE Multilin TABLE OF CONTENTS INDEX ...
Page 32: ...1 22 G60 Generator Protection System GE Multilin 1 5 USING THE RELAY 1 GETTING STARTED 1 ...
Page 160: ...4 30 G60 Generator Protection System GE Multilin 4 3 FACEPLATE INTERFACE 4 HUMAN INTERFACES 4 ...
Page 486: ...5 326 G60 Generator Protection System GE Multilin 5 10 TESTING 5 SETTINGS 5 ...
Page 518: ...6 32 G60 Generator Protection System GE Multilin 6 5 PRODUCT INFORMATION 6 ACTUAL VALUES 6 ...
Page 532: ...7 14 G60 Generator Protection System GE Multilin 7 2 TARGETS 7 COMMANDS AND TARGETS 7 ...
Page 748: ...D 10 G60 Generator Protection System GE Multilin D 1 IEC 60870 5 104 APPENDIX D D ...
Page 760: ...E 12 G60 Generator Protection System GE Multilin E 2 DNP POINT LISTS APPENDIX E E ...