GE Multilin
G60 Generator Protection System
B-35
APPENDIX B
B.4 MEMORY MAPPING
B
5898
...Repeated for FlexLogic Timer 20
58A0
...Repeated for FlexLogic Timer 21
58A8
...Repeated for FlexLogic Timer 22
58B0
...Repeated for FlexLogic Timer 23
58B8
...Repeated for FlexLogic Timer 24
58C0
...Repeated for FlexLogic Timer 25
58C8
...Repeated for FlexLogic Timer 26
58D0
...Repeated for FlexLogic Timer 27
58D8
...Repeated for FlexLogic Timer 28
58E0
...Repeated for FlexLogic Timer 29
58E8
...Repeated for FlexLogic Timer 30
58F0
...Repeated for FlexLogic Timer 31
58F8
...Repeated for FlexLogic Timer 32
Phase Time Overcurrent (Read/Write Grouped Setting)
5900
Phase Time Overcurrent 1 Function
0 to 1
---
1
F102
0 (Disabled)
5901
Phase Time Overcurrent 1 Signal Source
0 to 5
---
1
F167
0 (SRC 1)
5902
Phase Time Overcurrent 1 Input
0 to 1
---
1
F122
0 (Phasor)
5903
Phase Time Overcurrent 1 Pickup
0 to 30
pu
0.001
F001
1000
5904
Phase Time Overcurrent 1 Curve
0 to 16
---
1
F103
0 (IEEE Mod Inv)
5905
Phase Time Overcurrent 1 Multiplier
0 to 600
---
0.01
F001
100
5906
Phase Time Overcurrent 1 Reset
0 to 1
---
1
F104
0 (Instantaneous)
5907
Phase Time Overcurrent 1 Voltage Restraint
0 to 1
---
1
F102
0 (Disabled)
5908
Phase TOC 1 Block For Each Phase (3 items)
0 to 4294967295
---
1
F300
0
590F
Phase Time Overcurrent 1 Target
0 to 2
---
1
F109
0 (Self-reset)
5910
Phase Time Overcurrent 1 Events
0 to 1
---
1
F102
0 (Disabled)
5911
Reserved (3 items)
0 to 1
---
1
F001
0
Phase Instantaneous Overcurrent (Read/Write Grouped Setting) (2 modules)
5A00
Phase Instantaneous Overcurrent 1 Function
0 to 1
---
1
F102
0 (Disabled)
5A01
Phase Instantaneous Overcurrent 1 Signal Source
0 to 5
---
1
F167
0 (SRC 1)
5A02
Phase Instantaneous Overcurrent 1 Pickup
0 to 30
pu
0.001
F001
1000
5A03
Phase Instantaneous Overcurrent 1 Delay
0 to 600
s
0.01
F001
0
5A04
Phase Instantaneous Overcurrent 1 Reset Delay
0 to 600
s
0.01
F001
0
5A05
Phase IOC1 Block For Each Phase (3 items)
0 to 4294967295
---
1
F300
0
5A0B
Phase Instantaneous Overcurrent 1 Target
0 to 2
---
1
F109
0 (Self-reset)
5A0C
Phase Instantaneous Overcurrent 1 Events
0 to 1
---
1
F102
0 (Disabled)
5A0D
Reserved (6 items)
0 to 1
---
1
F001
0
5A13
...Repeated for Phase Instantaneous Overcurrent 2
Neutral Time Overcurrent (Read/Write Grouped Setting)
5B00
Neutral Time Overcurrent 1 Function
0 to 1
---
1
F102
0 (Disabled)
5B01
Neutral Time Overcurrent 1 Signal Source
0 to 5
---
1
F167
0 (SRC 1)
5B02
Neutral Time Overcurrent 1 Input
0 to 1
---
1
F122
0 (Phasor)
5B03
Neutral Time Overcurrent 1 Pickup
0 to 30
pu
0.001
F001
1000
5B04
Neutral Time Overcurrent 1 Curve
0 to 16
---
1
F103
0 (IEEE Mod Inv)
5B05
Neutral Time Overcurrent 1 Multiplier
0 to 600
---
0.01
F001
100
5B06
Neutral Time Overcurrent 1 Reset
0 to 1
---
1
F104
0 (Instantaneous)
5B07
Neutral Time Overcurrent 1 Block
0 to 4294967295
---
1
F300
0
5B09
Neutral Time Overcurrent 1 Target
0 to 2
---
1
F109
0 (Self-reset)
5B0A
Neutral Time Overcurrent 1 Events
0 to 1
---
1
F102
0 (Disabled)
5B0B
Reserved (6 items)
0 to 1
---
1
F001
0
Neutral Instantaneous Overcurrent (Read/Write Grouped Setting)
5C00
Neutral Instantaneous Overcurrent 1 Function
0 to 1
---
1
F102
0 (Disabled)
5C01
Neutral Instantaneous Overcurrent 1 Signal Source
0 to 5
---
1
F167
0 (SRC 1)
5C02
Neutral Instantaneous Overcurrent 1 Pickup
0 to 30
pu
0.001
F001
1000
5C03
Neutral Instantaneous Overcurrent 1 Delay
0 to 600
s
0.01
F001
0
Table B–10: MODBUS MEMORY MAP (Sheet 27 of 68)
ADDR
REGISTER NAME
RANGE
UNITS
STEP
FORMAT
DEFAULT
Summary of Contents for Multilin g60
Page 10: ...x G60 Generator Protection System GE Multilin TABLE OF CONTENTS INDEX ...
Page 32: ...1 22 G60 Generator Protection System GE Multilin 1 5 USING THE RELAY 1 GETTING STARTED 1 ...
Page 160: ...4 30 G60 Generator Protection System GE Multilin 4 3 FACEPLATE INTERFACE 4 HUMAN INTERFACES 4 ...
Page 486: ...5 326 G60 Generator Protection System GE Multilin 5 10 TESTING 5 SETTINGS 5 ...
Page 518: ...6 32 G60 Generator Protection System GE Multilin 6 5 PRODUCT INFORMATION 6 ACTUAL VALUES 6 ...
Page 532: ...7 14 G60 Generator Protection System GE Multilin 7 2 TARGETS 7 COMMANDS AND TARGETS 7 ...
Page 748: ...D 10 G60 Generator Protection System GE Multilin D 1 IEC 60870 5 104 APPENDIX D D ...
Page 760: ...E 12 G60 Generator Protection System GE Multilin E 2 DNP POINT LISTS APPENDIX E E ...