GE Multilin
G60 Generator Protection System
5-117
5 SETTINGS
5.4 SYSTEM SETUP
5
EXAMPLE: THE CREATION OF DIFFERENT DATA SETS
The aggregators allow the aggregation of phasors from multiple PMUs (with the same reporting rate) into a single custom
data set to optimize bandwidth when streaming.
Figure 5–44: EXAMPLE OF AGGREGATOR DATA SETS
CONFIGURATION EXAMPLE: CFG-2 BASED CONFIGURATION (USING IEC61850-90-5)
The G60 is expected to send the CFG-2 file (IEEE C37.118 config. file) upon request from the upstream synchrophasor
devices (e.g., P30) without stopping R-SV multicasting, see figure below. The primary domain controller (PDC) does not
need to use a stop/start data stream command if the UR protocol is set to IEC61850-90-5 prior to requesting the configura-
tion via CFG-2 (IEEE C37.118 config. file). The CFG-2 request from the P30 can be on TCP/IP or UDP/IP, however, R-SV
data streaming is only UDP multicasts (not TCP).
Figure 5–45: CFG-2 BASED CONFIGURATION SOLUTION
Summary of Contents for Multilin g60
Page 10: ...x G60 Generator Protection System GE Multilin TABLE OF CONTENTS INDEX ...
Page 32: ...1 22 G60 Generator Protection System GE Multilin 1 5 USING THE RELAY 1 GETTING STARTED 1 ...
Page 160: ...4 30 G60 Generator Protection System GE Multilin 4 3 FACEPLATE INTERFACE 4 HUMAN INTERFACES 4 ...
Page 486: ...5 326 G60 Generator Protection System GE Multilin 5 10 TESTING 5 SETTINGS 5 ...
Page 518: ...6 32 G60 Generator Protection System GE Multilin 6 5 PRODUCT INFORMATION 6 ACTUAL VALUES 6 ...
Page 532: ...7 14 G60 Generator Protection System GE Multilin 7 2 TARGETS 7 COMMANDS AND TARGETS 7 ...
Page 748: ...D 10 G60 Generator Protection System GE Multilin D 1 IEC 60870 5 104 APPENDIX D D ...
Page 760: ...E 12 G60 Generator Protection System GE Multilin E 2 DNP POINT LISTS APPENDIX E E ...