5-122
G60 Generator Protection System
GE Multilin
5.4 SYSTEM SETUP
5 SETTINGS
5
PMU 1 STYLE
: This setting selects whether synchrophasors are reported in rectangular (real and imaginary) coordinates
or in polar (magnitude and angle) coordinates. This setting complies with bit-0 of the FORMAT field of the IEEE C37.118
configuration frame.
With 90-5 PMU, the FORMAT and STYLE are Floating-point and Polar respectively, as specified in the IEC 61850
standard.
IEC 61850–90–5 PMU 1 CONFIGURATION
PATH: SETTINGS
SYSTEM SETUP
PHASOR MEASUREMENT
BASIC CONFIGURATION
PMU1
PMU 1 BASIC CONFIGURA-
TION
90 – 5 PMU 1 CONFIGURATION
PMU1 LDINST
: A user-defined visible string (maximum 64 char ASCII test) to assign Logical Device (LD) Inst for a PMU
LD.
As per IEC 61850-6 standard specification, the PMU LD Name is the concatenated combination (to total 64 charac-
ters) of IED Name (specified in IEC 61850 Server Settings) appended with PMU X LDINST string.
90–5 PMU 1
CONFIGURATION
PMU 1 LDINST:
PMU1
Range: 64 char ASCII text
NOTE
NOTE
Summary of Contents for Multilin g60
Page 10: ...x G60 Generator Protection System GE Multilin TABLE OF CONTENTS INDEX ...
Page 32: ...1 22 G60 Generator Protection System GE Multilin 1 5 USING THE RELAY 1 GETTING STARTED 1 ...
Page 160: ...4 30 G60 Generator Protection System GE Multilin 4 3 FACEPLATE INTERFACE 4 HUMAN INTERFACES 4 ...
Page 486: ...5 326 G60 Generator Protection System GE Multilin 5 10 TESTING 5 SETTINGS 5 ...
Page 518: ...6 32 G60 Generator Protection System GE Multilin 6 5 PRODUCT INFORMATION 6 ACTUAL VALUES 6 ...
Page 532: ...7 14 G60 Generator Protection System GE Multilin 7 2 TARGETS 7 COMMANDS AND TARGETS 7 ...
Page 748: ...D 10 G60 Generator Protection System GE Multilin D 1 IEC 60870 5 104 APPENDIX D D ...
Page 760: ...E 12 G60 Generator Protection System GE Multilin E 2 DNP POINT LISTS APPENDIX E E ...