5-282
G60 Generator Protection System
GE Multilin
5.7 CONTROL ELEMENTS
5 SETTINGS
5
b) BREAKER FLASHOVER
PATH: SETTINGS
CONTROL ELEMENTS
MONITORING ELEMENTS
BREAKER FLASHOVER 1(2)
The detection of the breaker flashover is based on the following condition:
1.
Breaker open,
2.
Voltage difference drop, and
3.
Measured flashover current through the breaker.
Furthermore, the scheme is applicable for cases where either one or two sets of three-phase voltages are available across
the breaker.
BREAKER
FLASHOVER 1
BKR 1 FLSHOVR
FUNCTION: Disabled
Range: Disabled, Enabled
MESSAGE
BKR 1 FLSHOVR SIDE 1
SRC: SRC 1
Range: SRC 1, SRC 2, SRC 3, SRC 4
MESSAGE
BKR 1 FLSHOVR SIDE 2
SRC: None
Range: None, SRC 1, SRC 2, SRC 3, SRC 4
MESSAGE
BKR 1 STATUS CLSD A:
Off
Range: FlexLogic operand
MESSAGE
BKR 1 STATUS CLSD B:
Off
Range: FlexLogic operand
MESSAGE
BKR 1 STATUS CLSD C:
Off
Range: FlexLogic operand
MESSAGE
BKR 1 FLSHOVR V PKP:
0.850 pu
Range: 0.000 to 1.500 pu in steps of 0.001
MESSAGE
BKR 1 FLSHOVR DIFF V
PKP: 1000 V
Range: 0 to 100000 V in steps of 1
MESSAGE
BKR 1 FLSHOVR AMP
PKP: 0.600 pu
Range: 0.000 to 1.500 pu in steps of 0.001
MESSAGE
BKR 1 FLSHOVR PKP
DELAY: 0.100 s
Range: 0.000 to 65.535 s in steps of 0.001
MESSAGE
BKR 1 FLSHOVR SPV A:
Off
Range: FlexLogic operand
MESSAGE
BKR 1 FLSHOVR SPV B:
Off
Range: FlexLogic operand
MESSAGE
BKR 1 FLSHOVR SPV C:
Off
Range: FlexLogic operand
MESSAGE
BKR 1 FLSHOVR BLOCK:
Off
Range: FlexLogic operand
MESSAGE
BKR 1 FLSHOVR
TARGET: Self-reset
Range: Self-reset, Latched, Disabled
MESSAGE
BKR 1 FLSHOVR
EVENTS: Disabled
Range: Disabled, Enabled
Summary of Contents for Multilin g60
Page 10: ...x G60 Generator Protection System GE Multilin TABLE OF CONTENTS INDEX ...
Page 32: ...1 22 G60 Generator Protection System GE Multilin 1 5 USING THE RELAY 1 GETTING STARTED 1 ...
Page 160: ...4 30 G60 Generator Protection System GE Multilin 4 3 FACEPLATE INTERFACE 4 HUMAN INTERFACES 4 ...
Page 486: ...5 326 G60 Generator Protection System GE Multilin 5 10 TESTING 5 SETTINGS 5 ...
Page 518: ...6 32 G60 Generator Protection System GE Multilin 6 5 PRODUCT INFORMATION 6 ACTUAL VALUES 6 ...
Page 532: ...7 14 G60 Generator Protection System GE Multilin 7 2 TARGETS 7 COMMANDS AND TARGETS 7 ...
Page 748: ...D 10 G60 Generator Protection System GE Multilin D 1 IEC 60870 5 104 APPENDIX D D ...
Page 760: ...E 12 G60 Generator Protection System GE Multilin E 2 DNP POINT LISTS APPENDIX E E ...