B-82
G60 Generator Protection System
GE Multilin
B.4 MEMORY MAPPING
APPENDIX B
B
F126
ENUMERATION: NO/YES CHOICE
0 = No, 1 = Yes
F127
ENUMERATION: LATCHED OR SELF-RESETTING
0 = Latched, 1 = Self-Reset
F128
ENUMERATION: CONTACT INPUT THRESHOLD
0 = 17 V DC, 1 = 33 V DC, 2 = 84 V DC, 3 = 166 V DC
F129
ENUMERATION: FLEXLOGIC TIMER TYPE
0 = millisecond, 1 = second, 2 = minute
F131
ENUMERATION: FORCED CONTACT OUTPUT STATE
0 = Disabled, 1 = Energized, 2 = De-energized, 3 = Freeze
F133
ENUMERATION: PROGRAM STATE
0 = Not Programmed, 1 = Programmed
F134
ENUMERATION: PASS/FAIL
0 = Fail, 1 = OK, 2 = n/a
F136
ENUMERATION: NUMBER OF OSCILLOGRAPHY RECORDS
0 = 31 x 8 cycles, 1 = 15 x 16 cycles, 2 = 7 x 32 cycles
3 = 3 x 64 cycles, 4 = 1 x 128 cycles
F137
ENUMERATION: USER-PROGRAMMABLE PUSHBUTTON
FUNCTION
0 = Disabled, 1 = Self-Reset, 2 = Latched
F141
ENUMERATION: SELF TEST ERRORS
1010
Field Ground
1011
Field Current
1012
Thermal overload protection 1
1013
Thermal overload protection 2
Bitmask
Element
Bitmask
Error
0
Any Self Tests
1
IRIG-B Failure
2
Port 1 Offline
3
Port 2 Offline
4
Port 3 Offline
5
Port 4 Offline
6
Port 5 Offline
7
Port 6 Offline
8
RRTD Communications Failure
9
Voltage Monitor
10
FlexLogic Error Token
11
Equipment Mismatch
12
Process Bus Failure
13
Unit Not Programmed
14
System Exception
15
Latching Output Discrepancy
17
Maintenance Alert 01
18
SNTP Failure
19
Maintenance Alert
20
Maintenance Alert
21
Maintenance Alert
22
Temperature Monitor
23
Process Bus Trouble
24
Brick Trouble
25
Field RTD Trouble
26
Field TDR Trouble
27
Remote Device Offline
28
Direct Device Offline
29
Maintenance Alert
30
Any Minor Error
31
Any Major Error
33
Maintenance Alert
64
Maintenance Alert
65
IEC 61850 Data Set
66
Aggregator Error
67
Unit Not Calibrated
68
Settings Save Error
69
SRAM Data Error
70
Program Memory
71
Watchdog Error
72
Low On Memory
73
Prototype Firmware
74
Module Failure 01
75
Module Failure 02
76
Module Failure 03
77
Module Failure 04
78
Module Failure 05
79
Module Failure 06
80
Module Failure 07
Summary of Contents for Multilin g60
Page 10: ...x G60 Generator Protection System GE Multilin TABLE OF CONTENTS INDEX ...
Page 32: ...1 22 G60 Generator Protection System GE Multilin 1 5 USING THE RELAY 1 GETTING STARTED 1 ...
Page 160: ...4 30 G60 Generator Protection System GE Multilin 4 3 FACEPLATE INTERFACE 4 HUMAN INTERFACES 4 ...
Page 486: ...5 326 G60 Generator Protection System GE Multilin 5 10 TESTING 5 SETTINGS 5 ...
Page 518: ...6 32 G60 Generator Protection System GE Multilin 6 5 PRODUCT INFORMATION 6 ACTUAL VALUES 6 ...
Page 532: ...7 14 G60 Generator Protection System GE Multilin 7 2 TARGETS 7 COMMANDS AND TARGETS 7 ...
Page 748: ...D 10 G60 Generator Protection System GE Multilin D 1 IEC 60870 5 104 APPENDIX D D ...
Page 760: ...E 12 G60 Generator Protection System GE Multilin E 2 DNP POINT LISTS APPENDIX E E ...