9-4
G60 Generator Protection System
GE Multilin
9.1 SETTING EXAMPLE
9 APPLICATION OF SETTINGS
9
9.1.7 LOSS OF EXCITATION
For the example system, we have the following values:
(EQ 9.7)
(EQ 9.8)
(EQ 9.9)
(EQ 9.10)
(EQ 9.11)
(EQ 9.12)
(EQ 9.13)
(EQ 9.14)
The voltage supervision setting will be determined by a system study and may be disabled on either element if required. VT
fuse failure should supervise this element.
The choice of source is not critical for this application. The NEUTRL source is chosen for the following setting changes.
Make the following changes in EnerVista UR Setup or through the
SETTINGS
GROUPED ELEMENTS
SETTING GROUP
1
LOSS OF EXCITATION
menu:
9.1.8 REVERSE POWER
The reverse power element should be set at ½ the rated motoring power. The pickup is calculated as follows:
(EQ 9.15)
For the example system:
If the example system has delta-connected VTs instead of wye-connected VTs, and say the VT secondary setting is set to
115 V instead of 66 V, then the setting value of S
min
is calculated as follows:
(EQ 9.16)
Z
b
sec
(
)
base kV
2
base MVA
---------------------------
CT ratio
VT ratio
---------------------
×
18 kV
(
)
2
211.765 MVA
------------------------------------
1600
157.5
---------------
×
15.54
Ω
=
=
=
X
d
′
(sec)
X
d
′
Z
b
(sec)
×
0.216 15.54
Ω
×
3.36
Ω
=
=
=
X
d
sec
(
)
X
d
Z
b
sec
(
)
×
1.967 15.54
Ω
×
30.57
Ω
=
=
=
CENTER 1
Z
b
sec
(
)
X
d
′
(sec)
+
2
-------------------------------------------------
15.54
Ω
3.36
Ω
+
2
-------------------------------------------
9.45
Ω
=
=
=
RADIUS 1
Z
b
sec
(
)
2
--------------------
15.54
Ω
2
----------------------
7.77
Ω
=
=
=
PICKUP DELAY 1
0.06 seconds
=
CENTER 2
X
d
sec
(
)
X
d
′
(sec)
+
2
-------------------------------------------------
30.57
Ω
3.36
Ω
+
2
-------------------------------------------
16.97
Ω
=
=
=
RADIUS 2
X
d
sec
(
)
2
---------------------
30.57
Ω
2
----------------------
15.28
Ω
=
=
=
S
min
1
2
---
Rated Motoring Power (primary watts)
3 Phase CT Primary Phase VT Ratio Phase VT Secondary
×
×
×
--------------------------------------------------------------------------------------------------------------------------------------------------------------------------
×
=
S
min
1
2
---
22 10
6
×
W
3 8000 A 157.5
×
66 V
×
×
---------------------------------------------------------------------
×
0.044 pu
=
=
S
min
1
2
---
22 10
6
×
W
3 8000 A 157.5
×
115 V
×
×
------------------------------------------------------------------------
×
0.0253 pu
=
=
Summary of Contents for Multilin g60
Page 10: ...x G60 Generator Protection System GE Multilin TABLE OF CONTENTS INDEX ...
Page 32: ...1 22 G60 Generator Protection System GE Multilin 1 5 USING THE RELAY 1 GETTING STARTED 1 ...
Page 160: ...4 30 G60 Generator Protection System GE Multilin 4 3 FACEPLATE INTERFACE 4 HUMAN INTERFACES 4 ...
Page 486: ...5 326 G60 Generator Protection System GE Multilin 5 10 TESTING 5 SETTINGS 5 ...
Page 518: ...6 32 G60 Generator Protection System GE Multilin 6 5 PRODUCT INFORMATION 6 ACTUAL VALUES 6 ...
Page 532: ...7 14 G60 Generator Protection System GE Multilin 7 2 TARGETS 7 COMMANDS AND TARGETS 7 ...
Page 748: ...D 10 G60 Generator Protection System GE Multilin D 1 IEC 60870 5 104 APPENDIX D D ...
Page 760: ...E 12 G60 Generator Protection System GE Multilin E 2 DNP POINT LISTS APPENDIX E E ...