GE Multilin
G60 Generator Protection System
3-57
3 HARDWARE
3.4 FIELD AND STATOR GROUND MODULES
3
Figure 3–63: GPM-F-R MODULE SHOWING TERMINAL BLOCKS
The following tables outline the pin assignments.
Table 3–11: GPM-F-R PIN ASSIGNMENTS FOR CONNECTOR A
PIN
LABEL
DEFINITION
1
A1
Not used
2
A2
Not used
3
A3
Injection secondary (F1)
4
A4
Not used
5
A5
Excitation secondary negative (F–)
6
A6
Not used
7
A7
Excitation secondary positive (F+)
Table 3–12: GPM-F-R PIN ASSIGNMENTS FOR CONNECTOR B
PIN
LABEL
DEFINITION
1
B1
Excitation primary positive (F2+)
2
B2
Not used
3
B3
Injection to excitation positive (F2)
Table 3–13: GPM-F-R PIN ASSIGNMENTS FOR CONNECTOR C
PIN
LABEL
DEFINITION
1
C1
Injection to excitation negative / excitation primary negative (F2–)
2
C2
Not used
3
C3
Not used
&RQQHFWRU$
&RQQHFWRU%
&RQQHFWRU&
$&'5
Summary of Contents for Multilin g60
Page 10: ...x G60 Generator Protection System GE Multilin TABLE OF CONTENTS INDEX ...
Page 32: ...1 22 G60 Generator Protection System GE Multilin 1 5 USING THE RELAY 1 GETTING STARTED 1 ...
Page 160: ...4 30 G60 Generator Protection System GE Multilin 4 3 FACEPLATE INTERFACE 4 HUMAN INTERFACES 4 ...
Page 486: ...5 326 G60 Generator Protection System GE Multilin 5 10 TESTING 5 SETTINGS 5 ...
Page 518: ...6 32 G60 Generator Protection System GE Multilin 6 5 PRODUCT INFORMATION 6 ACTUAL VALUES 6 ...
Page 532: ...7 14 G60 Generator Protection System GE Multilin 7 2 TARGETS 7 COMMANDS AND TARGETS 7 ...
Page 748: ...D 10 G60 Generator Protection System GE Multilin D 1 IEC 60870 5 104 APPENDIX D D ...
Page 760: ...E 12 G60 Generator Protection System GE Multilin E 2 DNP POINT LISTS APPENDIX E E ...