5-220
G60 Generator Protection System
GE Multilin
5.6 GROUPED ELEMENTS
5 SETTINGS
5
,
Figure 5–109: THREE-POLE BREAKER FAILURE, INITIATE
827067A5.cdr
AND
OR
OR
AND
AND
OR
OR
Seal In Path
AND
TO SHEET 2 OF 2
(Initiated)
TO SHEET 2 OF 2
(827068.cdr)
BF1 FUNCTION:
Disable=0
Enable=1
SETTING
BF1 BLOCK:
Off=0
SETTING
BF1 INITIATE:
Off=0
SETTING
BF1 USE SEAL-IN:
YES=1
NO=0
SETTING
BF1 USE AMP SUPV:
YES=1
NO=0
SETTING
IA
IB
IN
IC
BF1 SOURCE:
SETTING
IA
³
PICKUP
RUN
BF1 PH AMP SUPV
SETTINGS
PICKUP:
BF1 N AMP SUPV
PICKUP:
RUN
RUN
RUN
IB
³
PICKUP
IC
³
PICKUP
IN
³
PICKUP
BKR FAIL 1 RETRIP
FLEXLOGIC OPERAND