GE Multilin
G60 Generator Protection System
B-25
APPENDIX B
B.4 MEMORY MAPPING
B
3E8B
...Repeated for Field Shared Output 8
3E98
...Repeated for Field Shared Output 9
3EA5
...Repeated for Field Shared Output 10
3EB2
...Repeated for Field Shared Output 11
3EBF
...Repeated for Field Shared Output 12
3ECC
...Repeated for Field Shared Output 13
3ED9
...Repeated for Field Shared Output 14
3EE6
...Repeated for Field Shared Output 15
3EF3
...Repeated for Field Shared Output 16
Field Unit RTDs (Read/Write Setting) (8 modules)
3F00
Field Unit RTD 1Name
0 to 1
---
1
F205
"RTD 1"
3F06
Field Unit RTD 1 Origin
0 to 24
---
1
F253
0 (None)
3F07
Field Unit RTD 1 Type
0 to 2
---
1
F259
0 (100 Ohm
Nickel)
3F08
...Repeated for Field Unit RTD 2
3F10
...Repeated for Field Unit RTD 3
3F18
...Repeated for Field Unit RTD 4
3F20
...Repeated for Field Unit RTD 5
3F28
...Repeated for Field Unit RTD 6
3F30
...Repeated for Field Unit RTD 7
3F38
...Repeated for Field Unit RTD 8
Field Unit Transducers (Read/Write Setting) (8 modules)
3F40
Field Unit Transducer 1 Name
0 to 1
---
1
F205
"TRD 1"
3F46
Field Unit Transducer 1 Origin
0 to 24
---
1
F253
0 (None)
3F47
Field Unit Transducer 1 Range
0 to 9
---
1
F246
6 (0...20mA)
3F48
Field Unit Transducer 1 Min Value
-9999.999 to 9999.999
---
0.001
F004
0
3F4A
Field Unit Transducer 1 Max Value
-9999.999 to 9999.999
---
0.001
F004
100000
3F4C
Field Unit Transducer 1 Units
---
---
---
F206
(none)
3F4F
...Repeated for Field Unit Transducer 2
3F5E
...Repeated for Field Unit Transducer 3
3F6D
...Repeated for Field Unit Transducer 4
3F7C
...Repeated for Field Unit Transducer 5
3F8B
...Repeated for Field Unit Transducer 6
3F9A
...Repeated for Field Unit Transducer 7
3FA9
...Repeated for Field Unit Transducer 8
Field Unit Identifiers (Read Only) (8 modules)
3FB8
Attached Field Unit 1 Serial Number
---
---
1
F205
(none)
3FBE
Attached Filed Unit 1 Port Number
---
---
1
F001
0
3FBF
Attached Field Unit 1 Type
0 to 3
---
1
F243
0 (CC-05)
3FC0
Field Unit 1 Status
0 to 4
---
1
F262
0 (Disabled)
3FC1
...Repeated for Field Unit 2
3FCA
...Repeated for Field Unit 3
3FD3
...Repeated for Field Unit 4
3FDC
...Repeated for Field Unit 5
3FE5
...Repeated for Field Unit 6
3FEE
...Repeated for Field Unit 7
3FF7
...Repeated for Field Unit 8
Passwords (Read/Write Command)
4000
Command Password Setting
0 to 4294967295
---
1
F202
(none)
Passwords (Read/Write Setting)
400A
Setting Password Setting
0 to 4294967295
---
1
F202
(none)
Passwords (Read/Write)
4014
Command Password Entry
0 to 4294967295
---
1
F202
(none)
401E
Setting Password Entry
0 to 4294967295
---
1
F202
(none)
Table B–10: MODBUS MEMORY MAP (Sheet 17 of 68)
ADDR
REGISTER NAME
RANGE
UNITS
STEP
FORMAT
DEFAULT
Summary of Contents for Multilin g60
Page 10: ...x G60 Generator Protection System GE Multilin TABLE OF CONTENTS INDEX ...
Page 32: ...1 22 G60 Generator Protection System GE Multilin 1 5 USING THE RELAY 1 GETTING STARTED 1 ...
Page 160: ...4 30 G60 Generator Protection System GE Multilin 4 3 FACEPLATE INTERFACE 4 HUMAN INTERFACES 4 ...
Page 486: ...5 326 G60 Generator Protection System GE Multilin 5 10 TESTING 5 SETTINGS 5 ...
Page 518: ...6 32 G60 Generator Protection System GE Multilin 6 5 PRODUCT INFORMATION 6 ACTUAL VALUES 6 ...
Page 532: ...7 14 G60 Generator Protection System GE Multilin 7 2 TARGETS 7 COMMANDS AND TARGETS 7 ...
Page 748: ...D 10 G60 Generator Protection System GE Multilin D 1 IEC 60870 5 104 APPENDIX D D ...
Page 760: ...E 12 G60 Generator Protection System GE Multilin E 2 DNP POINT LISTS APPENDIX E E ...