3-210
UR FAMILY – COMMUNICATIONS GUIDE
MODEL IMPLEMENTATION CONFORMANCE STATEMENT (MICS)
CHAPTER 3: IEC 61850 COMMUNICATION
3
Activated
SPS
Activated. In this logical node, indicates position of a pushbutton. When "true", the
pushbutton is asserted state; when "false", the pushbutton is in a released state.
CONTROL PUSH BUTTON 1 ON operand.
PUSHBUTTON 1 ON operand.
CtlPshIHMI, UsrPbIHMI
Adif
CMV
Differential current (sum of the three phase currents and the ground (fourth)
current. Restricted ground differential if the fourth current measures the ground
current in a grounded wye winding. Measures CT secondary circuit trouble if
fourth current measures the CT secondary neutral current.
SRC 1 Differential Ground Current phasor, in primary volts.
ACsrcMMXU
Agnd
CMV
Ground current (fourth input in a current AC bank).
SRC 1 Ground Current phasor, in primary amperes.
ACsrcMMXN
AgndRMS
MV
Ground current RMS (fourth input in a current AC bank).
SRC 1 Ground Current RMS, in primary amperes.
ACsrcMMXN
AlgCap
SPC
Command for the Hi-Z Oscillography Force Algorithm Capture
HiZPHIZ
AlmInd
SPS
An LED.
The LED ALARM operand.
LEDsIHMI
AmpInd
SPS
An LED.
The LED CURRENT operand.
LEDsIHMI
AnFailBeh
ENG
Setting to select the behavior of the RxGOOSE Analog when the sending device is
offline: 0 = Default Value, 1 = Last Known
GGIO3
AnFailVal
ASG
The value of the RxGOOSE Analog when the sending device is offline and the
FailBeh is set to "Default Value"
GGIO3
AnOutput1
MV
Analog output
Cmp8BtGAPC
AnyPBOn
SPS
Indicates ANY PB ON operand state. When any of the user pushbuttons is
asserted, status is "true"; when none of the user pushbuttons are asserted, status
is "false."
UsrPbIHMI
AnyErr
SPS
Any of the self-test errors generated. The ANY SELF TESTS operand.
LPHD
AnyGpsFail
SPS
The GPS signal failed or is not configured properly at any terminal.
The 87L DIFF GPS FAIL operand, which becomes On when the GPS signal failed or
is not configured properly at any terminal.
LinDfPDIF
AnyPoleOpn
SPS
At least one pole is open. The BREAKER 1 ANY P OPEN operand.
Bkr0XCBR
AnyShotCnt
SPS
The first breaker close signal has been issued.
The AR SHOT CNT greater than zero operand.
Rec13pRREC
APPID
ING
Expected value of APPID field in messages subscribed to by RxGOOSE#
The RxGOOSE1 ETYPE APPID setting.
LGOS
ArBlk1
SPS
Autoreclose Breaker number indicated by the data instance number is
temporarily disabled.
The AR BKR1 BLK operand and the AR1 BLK FROM MAN CLS operand.
Rec13pRREC, Rec3pRREC
ArcConfid1
INS
Represents the Arc Confidence in percentage for Phase A, B, C, or N
HiZPHIZ
ArcSuspect
ACT
Indicates suspected element has operated
HiZPHIZ
AresRMS
MV
Residual Current RMS.
SRC 1 Neutral Current RMS, in primary amperes.
ACsrcMMXU
ArLO
SPS
Autoreclose is locked out. The AR LO operand.
Rec13pRREC, Rec3pRREC
Armed
SPS
Accidental energization. Occurs when the generator is offline with no fault
involved. The ACCDNT ENRG ARMED operand.
AcdEnrPIOC
ArMod1
SPS
Autoreclosec mode equals to the number indicated by the data instance number,
in this case 1 and 3 pole mode. The AR MODE = 1 operand.
Rec13pRREC
ArRip
SPS
Autoreclose is in progress. The AR RIP operand.
Rec13pRREC, Rec3pRREC
ASupn1
SPS
Indicates the state of current supervision.
The PHS DIST Z1 SUPN AB/BC/CA operand in Phase-To-Phase.
PhsDisPDIS
Asymmetry
SPS
Communications channel asymmetry detected.
The 87L DIFF CH ASYM DET operand, which becomes On when the differential
element's has detected substantial communications channel asymmetry.
LinDfPDIF
AutoMod
SPS
Capacitor control in auto mode. The CAP 1 IN AUTO operand.
CapCtlGAPC
Data object
name
CDC
Semantics
Used in logical nodes…