CHAPTER 3: IEC 61850 COMMUNICATION
MODEL IMPLEMENTATION CONFORMANCE STATEMENT (MICS)
UR FAMILY – COMMUNICATIONS GUIDE
3-93
3
3.5.2.56 Phase directional (PhsDir)
This element is instantiated in the following products: B30, C70, D30, D60, F60, G30, G60, L30, L60, L90, M60, N60, T60.
Table 3-101: Phase directional data objects
3.5.2.57 Phase distance (PhsDis)
This element is instantiated in the following products: D30, D60, G60, L60, L90, T60.
Table 3-102: Phase distance data objects
Op
ACT
CUR BAL # OP operands (including
individual three phases of this stage).
R
general
BOOLEAN
ST Logical OR of data attributes
phsA, phsB, phsC
R
phsA
BOOLEAN
ST CUR BAL # STG$A OP
R
phsB
BOOLEAN
ST CUR BAL # STG$B OP
R
phsC
BOOLEAN
ST CUR BAL # STG$C OP
R
BlkRef
γ
ORG
CUR UNBL # BLK STG$ setting for setting
group
γ
.
R
setSrcRef
ObjectReference SP CUR UNBL # BLK STG$ for group
γ
.
reference to the data attribute to input
R/C
setSrcCB
ObjectReference SP
source GoCB of input if via GOOSE
R/C
LNName: PhsDirRDIR#
LDevice inst: Prot
UR element: Phase Directional element # (ANSI 67P)
data obj. data attribute
Type
FC UR Name
Description
R/W/C
Dir
ACD
PH DIR # BLK operand, which becomes
On when phase current is flowing in the
set direction
R
general
BOOLEAN
ST PH DIR # BLK
R
dirGeneral
ENUMERATED
ST
0, the code for unknown. It is unknown as
the element may be connected/
configured to look forward or backward
R
phsA
BOOLEAN
ST PH DIR # BLK A
R
dirPhsA
ENUMERATED
ST
0, the code for unknown
R
phsB
BOOLEAN
ST PH DIR # BLK B
R
dirPhsB
ENUMERATED
ST
0, the code for unknown
R
phsC
BOOLEAN
ST PH DIR # BLK C
R
dirPhsC
ENUMERATED
ST
0, the code for unknown
R
BlkRef
γ
ORG
PHASE DIR # BLOCK setting for setting
group
γ
.
R
setSrcRef
ObjectReference SP PHASE DIR # BLOCK for group
γ
. reference to the data attribute to input
R/C
setSrcCB
ObjectReference SP
source GoCB of input if via GOOSE
R/C
LNName: PhsDisPDIS#
LDevice inst: Prot
UR element: Phase Distance Z# settings
data obj. data attribute
Type
FC UR Name
Description
R/W/C
Str
ACD
PHS DIST Z# PKP operand in Phase-To-
Phase
R
general
BOOLEAN
ST PH DIST Z# PKP
R
dirGeneral
ENUMERATED
ST
1(Forward) if PHS DIST Z DIR value is
Forward, 2 (backward) if PHS DIST Z1 DIR
value is Reverse, and otherwise 0
(unknown).
R
Op
ACT
PHS DIST Z# OP operand in Phase-To-
Phase
R
general
BOOLEAN
ST PHS DIST Z# OP
R
StrPhs
φ
SPS
PHS DIST Z# PKP
θ
operand in Phase-To-
Phase
R
stVal
BOOLEAN
ST PHS DIST Z# PKP
θ
R
LNName: PhAUn$PTOC#
LDevice inst: Prot
UR element: Phase Current Unbalance element # Stage $
data obj. data attribute
Type
FC UR Name
Description
R/W/C