CHAPTER 2: MODBUS COMMUNICATION
MEMORY MAP
UR FAMILY – COMMUNICATIONS GUIDE
2-107
2
"
7460
...Repeated for Breaker Failure 19
"
7490
...Repeated for Breaker Failure 20
"
74C0
...Repeated for Breaker Failure 21
"
74F0
...Repeated for Breaker Failure 22
"
7520
...Repeated for Breaker Failure 23
"
7550
...Repeated for Breaker Failure 24
Ground Distance (Read/Write Grouped Setting) (3 or 5 Modules)
D30, D60, L60,
L90, T60
7130
Ground Distance Zone 1 Function
0 to 1
---
1
F102
0 (Disabled)
"
7131
Ground Distance Zone 1 Current
Supervision
0.05 to 30
pu
0.001 F001
200
"
7132
Ground Distance Zone 1 Reach
0.02 to 500
ohms
0.01
F001
200
"
7133
Ground Distance Zone 1 Direction
0 to 2
---
1
F154
0 (Forward)
"
7134
Ground Distance Zone 1 Comparator Limit 30 to 90
degrees 1
F001
90
"
7135
Ground Distance Zone 1 Delay
0 to 65.535
s
0.001 F001
0
"
7136
Ground Distance Zone 1 Block
0 to 4294967295
---
1
F300
0
"
7138
Ground Distance Zone 1 Target
0 to 2
---
1
F109
0 (Self-reset)
"
7139
Ground Distance Zone 1 Events
0 to 1
---
1
F102
0 (Disabled)
"
713A
Ground Distance Zone 1 Shape
0 to 1
---
1
F120
0 (Mho)
"
713B
Ground Distance Zone 1 Z0 Z1 Magnitude
0 to 10
---
0.01
F001
270
"
713C
Ground Distance Zone 1 Z0 Z1 Angle
-90 to 90
degrees 1
F002
0
"
713D
Ground Distance Zone 1 RCA
30 to 90
degrees 1
F001
85
"
713E
Ground Distance Zone 1 DIR RCA
30 to 90
degrees 1
F001
85
"
713F
Ground Distance Zone 1 DIR Comp Limit
30 to 90
degrees 1
F001
90
"
7140
Ground Distance Zone 1 Quad Right Blinder 0.02 to 500
ohms
0.01
F001
1000
"
7141
Ground Distance Zone 1 Quad Right Blinder
RCA
60 to 90
degrees 1
F001
85
"
7142
Ground Distance Zone 1 Quad Left Blinder 0.02 to 500
ohms
0.01
F001
1000
"
7143
Ground Distance Zone 1 Quad Left Blinder
RCA
60 to 90
degrees 1
F001
85
"
7144
Ground Distance Zone 1 Z0M Z1 Magnitude 0 to 7
---
0.01
F001
0
"
7145
Ground Distance Zone 1 Z0M Z1 Angle
-90 to 90
degrees 1
F002
0
"
7146
Ground Distance Zone 1 Voltage Level
0 to 5
pu
0.001 F001
0
"
7147
Ground Distance Zone 1 Non-
Homogeneous Angle
-40 to 40
degrees 0.1
F002
0
"
7148
Ground Distance Zone 1 POL Current
0 to 1
---
1
F521
0 (Zero-seq)
"
7149
Ground Distance Zone 1 Reverse Reach
0.02 to 500
ohms
0.01
F001
200
"
714A
Ground Distance Zone 1 Reverse Reach
RCA
30 to 90
degrees 1
F001
85
"
714B
Reserved (7 items)
0 to 65535
---
1
F001
0
"
7152
...Repeated for Ground Distance Zone 2
"
7174
...Repeated for Ground Distance Zone 3
D30, D60, L90,
T60
7196
...Repeated for Ground Distance Zone 4
"
71B8
...Repeated for Ground Distance Zone 5
Line Pickup (Read/Write Grouped Setting)
D30, D60, L60,
L90
71E0
Line Pickup Function
0 to 1
---
1
F102
0 (Disabled)
"
71E1
Line Pickup Signal Source
0 to 5
---
1
F167
0 (SRC 1)
Products
Address Register name
Range
Units
Step
Format
Default