3-166
UR FAMILY – COMMUNICATIONS GUIDE
MODEL IMPLEMENTATION CONFORMANCE STATEMENT (MICS)
CHAPTER 3: IEC 61850 COMMUNICATION
3
3.5.4.8 Field contact inputs (FCIn)
This element is instantiated in all UR products (B30, B90, C30, C60, C70, D30, D60, F35, F60, G30, G60, L30, L60, L90, M60,
N60, T35, T60).
Table 3-181: Field contact input data objects
ctlModel
CtlModels
CF
0
R
BlkOpn
SPC
Disconnect switch open commands
blocked from all sources including
protection
R
stVal
BOOLEAN
ST Disc0XSWI#.BlkOpn.stVal
R
ctlModel
CtlModels
CF
0
R
BlkCls
SPC
Disconnect switch close commands
blocked from all sources
R
stVal
BOOLEAN
ST Disc0XSWI#.BlkCls.stVal
R
ctlModel
CtlModels
CF
0
R
InRef1
ORG
SWITCH #
φ
A/3P CLSD setting” if
Θ
=”1”,
“SWITCH #
φ
B CLSD setting” if
Θ
=”2”, or
“SWITCH #
φ
C CLSD setting” if
Θ
=”3
R
GEORG
R
setSrcRef
ObjectReference SP SWITCH #
φ
A/3P CLSD if
Θ
=”1”,
SWITCH #
φ
B CLSD if
Θ
=”2”, or
SWITCH #
φ
C CLSD if
Θ
=”3”
reference to the data attribute to input
R/C
VISIBLE
STRING255
SP
R/C
setSrcCB
ObjectReference SP
source GoCB of input if via GOOSE
R/C
VISIBLE
STRING255
SP If reference is external to this
IED, mapped to the source’s
GOOSE control block, else empty
string
R/C
cdcNs
VISIBLE
STRING255
EX Name of the GE Multilin
namespace at the time of this
firmware release
R
cdcName
VISIBLE
STRING255
EX GEORG
R
InRef2
ORG
SWITCH #
φ
A/3P OPND setting” if
Θ
=”1”,
“SWITCH #
φ
B OPND setting” if
Θ
=”2”, or
“SWITCH #
φ
C OPND setting” if
Θ
=”3
R
GEORG
R
setSrcRef
ObjectReference SP SWITCH #
φ
A/3P OPND if
Θ
=”1”,
SWITCH #
φ
B OPND if
Θ
=”2”, or
SWITCH #
φ
C OPND if
Θ
=”3”
reference to the data attribute to input
R/C
VISIBLE
STRING255
SP
R/C
setSrcCB
ObjectReference SP
source GoCB of input if via GOOSE
R/C
VISIBLE
STRING255
SP If reference is external to this
IED, mapped to the source’s
GOOSE control block, else empty
string
R/C
cdcNs
VISIBLE
STRING255
EX Name of the GE Multilin
namespace at the time of this
firmware release
R
cdcName
VISIBLE
STRING255
EX GEORG
R
LNName: FCInGGIO1
LDevice inst: System
UR element: Field Contact Inputs
data obj. data attribute
Type
FC UR Name
Description
R/W/C
Ind
Θ
SPS
FCI
Θ
On operand value
R
stVal
BOOLEAN
ST FCI
Θ
On
R
LNName: Disc
Θ
XSWI#
LDevice inst: System
UR element: Disconnect Control element #
data obj. data attribute
Type
FC UR Name
Description
R/W/C